Equflow 6010BCPM Pulse Input Batch Controller Instruction Manual
7
Relay Reset
User selectable via front panel buttons,
digital inputs, or PC
1. Automatic reset only (non-latching),
when the input passes the reset point
or total is reset to zero.
2. Aut manual reset at any time
(non-latching)
3. Manual reset only, at any time
(latching)
4.
Manual reset only after alarm condition
has cleared (L)
Note: Digital inputs may be assigned to
acknowledge relays programmed for manual
reset. It is not recommended to change the
functions of front panel buttons to manual
reset.
Alarm Time
Delay
0 to 999.9 seconds, on & off relay time
delays
Programmable and independent for each
relay.
Fail-Safe
Operation
Programmable and independent for each
relay.
Note: Relay coil is energized in non-alarm
condition.
In case of power failure, relay will go
to alarm state.
Alarm Auto
Initialization
When power is applied to the controller,
relays will reflect the state of the input to the
controller.
1
1. Alarms are active only when the batch is running.
2. These functions are not functional when the unit is being
used as a batch controller with total set to yes.
Modbus
®
RTU Serial Communications
Slave Id
1
– 247 (Controller address)
Baud Rate
300 - 19,200 bps
Transmit
Time Delay
Programmable between 0 and 199 ms
Data
8 bit (1 start bit, 1 or 2 stop bits)
Parity
Even, Odd, or None with 1 or 2 stop bits
Byte-To-Byte
Timeout
0.01
– 2.54 second
Turn Around
Delay
Less than 2 ms (fixed)
Note: Refer to the Modbus Register Tables located at
www.equflow.com for details.
60101044 Digital Input & Output Expansion
Module
Channels
4 digital inputs & 4 digital outputs per
module
System
Up to 2 modules for a total of 8 inputs & 8
outputs
Digital Input
Logic High
3 to 5 VDC
Digital Input
Logic Low
0 to 1.25 VDC
Digital Output
Logic High
3.1 to 3.3 VDC
Digital Output
Logic Low
0 to 0.4 VDC
Source
Current
10 mA maximum output current
Sink Current
1.5 mA minimum input current
+5 V Terminal
To be used as pull-up for digital inputs only
Connect normally open pushbuttons across
+5 V & DI 1-4.
MeterView Pro
System Re-
quirements
Microsoft
®
Windows
®
XP/Vista/7/8/10
Communica-
tions
USB 2.0 (Standard USB A to Micro USB
B)
Configuration
Configure meters one at a time