![Epever SolarV TRIRON Series User Manual Download Page 14](http://html1.mh-extra.com/html/epever/solarv-triron-series/solarv-triron-series_user-manual_2417317014.webp)
Copyright© 2022 SolarV GmbH All rights reserved.
10
¾
Battery and Load Wire Size
The battery and load wire size must conform to the rated current. The reference size is as below:
Model
Rated charge
current
Rated
discharge
current
Battery wire size
Load wire size
TRIRON1206N
TRIRON1210N
10A
10A
4mm
2
/12AWG
4mm
2
/12AWG
TRIRON2206N
TRIRON2210N
20A
20A
6mm
2
/10AWG
6mm
2
/10AWG
TRIRON3210N
TRIRON3215N
30A
30A
10mm
2
/8AWG
10mm
2
/8AWG
TRIRON4210N
TRIRON4215N
40A
40A
16mm
2
/6AWG
16mm
2
/6AWG
CAUTION
The wire size is only for reference. Suppose there is a long distance between the
PV array, the controller, and the battery. In that case, larger wires can be used to
reduce the voltage drop and improve performance.
2.4 Mounting
WARNING
x
Risk of explosion! Never install the controller in a sealed enclosure with
flooded batteries! Do not install in a confined area where battery gas can
accumulate.
x
Risk of electric shock! The PV array can produce open-circuit voltages over
100V in sunlight when wiring the solar modules.
CAUTION
The controller requires at least 150mm of clearance above and below for
proper airflow. Ventilation is highly recommended if mounted in an enclosure.