Digitax ST User Guide
161
Issue Number: 5
12.16.3 Digitax ST Plus
Table 12-7 Digitax ST Plus
Automation (I/O Expansion) module category
Parameter
Range(
Ú
)
Default(
Ö
)
Type
17.01
Motion processor ID
0 to 599
RO Uni
PT US
17.02
Motion processor software version
0.00 to 99.99
RO Uni
NC PT
17.03
DPL program status
None (0), Stop (1), Run (2), Trip (3)
RO Txt
NC PT
17.04
Available system resource
0 to 100
RO Uni
NC PT
17.05
RS485 address
0 to 255
11
RW Uni
US
17.06
RS485 mode
0 to 255
1
RW Uni
US
17.07
RS485 baud rate
300 (0), 600 (1), 1200 (2), 2400 (3), 4800 (4),
9600 (5), 19200 (6), 38400 (7), 57600 (8),
115200 (9) baud
4800 (4)
RW Txt
US
17.08
RS485 Turnaround delay
0 to 255 ms
2
RW Uni
US
17.09
RS485 Tx enable delay
0 to 1 ms
0
RW Uni
US
17.10
DPL Print Routing
SYPT: OFF (0), RS485: On (1)
SYPT: OFF (0)
RW Bit
US
17.11
Clock tick time (ms)
0 to 200
10
RW Uni
US
17.12
Motion engine sample rate
dISAbLEd (0), 0.25 ms (1), 0.5 ms (2), 1 ms (3),
2 ms (4), 4 ms (5), 8 ms (6)
dISAbLEd (0)
RW Txt
US
17.13
Enable autorun
OFF (0) or On (1)
On (1)
RW Bit
US
17.14
Global run time trip enable
OFF (0) or On (1)
OFF (0)
RW Bit
US
17.15
Disable reset on trip cleared
OFF (0) or On (1)
OFF (0)
RW Bit
US
17.16
Encoder data update rate
0 to 3
0
RW Uni
US
17.17
Enable parameter over range trips
OFF (0) or On (1)
OFF (0)
RW Bit
US
17.18
Watchdog enable
OFF (0) or On (1)
OFF (0)
RW Bit
US
17.19
Save request
OFF (0) or On (1)
OFF (0)
RW Bit
NC
17.20
Enable power down save
OFF (0) or On (1)
OFF (0)
RW Bit
US
17.21
Enable menu 20 save and
restore
OFF (0) or On (1)
OFF (0)
RW Bit
US
17.22
CTNet Token Ring ID
0 to 255
0
RW Uni
US
17.23
CTNet node address
0 to 255
0
RW Uni
US
17.24
CTNet baud rate
5.000 (0), 2.500 (1), 1.250 (2), 0.625 (3)
2.500 (1)
RW Txt
US
17.25
CTNet sync setup
0,000 to 9,999
0,000
RW Uni
US
17.26
CTNet easy mode - first cyclic
parameter destination node
0 to 25,503
0
RW Uni
US
17.27
CTNet easy mode - first cyclic source
parameter
0 to 9,999
0
RW Uni
US
17.28
CTNet easy mode - second cyclic
parameter destination node
0 to 25,503
0
RW Uni
US
17.29
CTNet easy mode - second cyclic
source parameter
0 to 9,999
0
RW Uni
US
17.30
CTNet easy mode - third cyclic
parameter destination node
0 to 25,503
0
RW Uni
US
17.31
CTNet easy mode - third cyclic source
parameter
0 to 9,999
0
RW Uni
US
17.32
CTNet easy mode set-up - Transfer
slot 1 destination parameter
0 to 9,999
0
RW Uni
US
17.33
CTNet easy mode set-up - Transfer
slot 2 destination parameter
0 to 9,999
0
RW Uni
US
17.34
CTNet easy mode set-up - Transfer
motion processor destination
parameter
0 to 9,999
0
RW Uni
US
17.35
CTNet sync event task ID
Disabled (0), Event (1), Event1 (2), Event2 (3),
Event3 (4)
Disabled (0)
RW Txt
US
17.36
CTNet diagnostic parameter
RO Uni
NC PT
17.37
Reject download if drive enabled
OFF (0) or On (1)
OFF (0)
RW Bit
US
17.38
Do not trip drive on APC run-time error
OFF (0) or On (1)
OFF (0)
RW Bit
US
17.39
Inter-UT70 synchronization status
0 to 3
0
RO Uni
NC
17.40
Inter-UT70 master transfer mode
0 to 10
1
RW Uni
US
17.41
Indexer control
0 to 3
0
RW Uni
NC
17.42
Freeze main drive position
OFF (0) or On (1)
OFF (0)
RW Bit
US
17.43
Freeze invert
OFF (0) or On (1)
OFF (0)
RW Bit
US
17.44
Task priority level
0 to 255
0
RW Uni
US
17.45
User set-up parameter 1
0
RO Uni
NC PT
17.46
User set-up parameter 2
0
RO Uni
NC PT
17.47
User set-up parameter 3
0
RO Uni
NC PT
17.48
DPL line number in error
0 to 2,147,483,647
0
RO Uni
NC PT
17.49
User program ID
-32,767 to +32,768
0
RO Bi
NC PT
17.50
Solutions Module error status*
0 to 255
RO Uni
NC PT
17.51
Solutions Module software sub-version
0 to 99
RO Uni
NC PT
RW Read / Write
RO
Read only
Uni
Unipolar
Bi
Bi-polar
Bit
Bit parameter
Txt
Text string
FI
Filtered
DE
Destination
NC
Not copied
RA
Rating dependent
PT
Protected
US
User save
PS
Power down save