technical data
*Enware products are to be installed in accordance
with the Plumbing Code of Australia (PCA), AS/NZS3500
and the manufacturer’s instructions. Installations
not complying with PCA, AS/NZS 3500 and the
manufacturer’s instructions may void the product and
performance warranty provisions.
To effectively control microbial hazards during system
design, installation, commissioning and maintenance,
the requirements outlined in AS/NZS3666 and local
legislation shall be adhered to
AQUABLEND SQX THERMOSTATIC MIXERS are
WaterMark approved to AS4032.1
and should be
installed using the appropriate Standard, Code of
Practice and legislation applicable to each state.
Thermostatic mixing valves must be installed by a
qualified plumber.
Prior to installation the system must be checked to
ensure the system operating conditions fall within
the recommended operating range specified in above
Technical Data. If the valve is not installed correctly it will
not function correctly and may put users in danger and
valve warranty may also be void.
To ensure the Thermostatic mixer operates correctly it
is necessary that pipework be thoroughly flushed with
clean water before installation as per AS/NZS 3500.1.
This will remove any physical contaminants from
pipework, ensuring trouble-free operation.
Before installation ensure all operating and dimensional
specifications are suitable for the intended installation.
If debris is an ongoing problem, the use of strainers (40
mesh) is recommended. A Pressure reduction valve may
be required to comply with recommended maximum
supply pressure.
T
HE FOLLOWING CLAUSES MUST BE OBSERVED FOR A
COMPLIANT INSTALLATION AND CORRECT OPERATION:
Plumbing Code of Australia: Part B1 Cold Water Services
AS/NZS 3500.1-2003 Water Services;
• Section 1.6(a) Facilities for people with Disabilities
• Section 3.3.2 Pressure at outlets (min 50kPa)
• Section 3.3.4 Maximum pressure within buildings
(500kPa static)
• Section 3.4 Velocity Requirement (Max 3.0m/s)
• Section 16 Testing and Commissioning; Flushing,
Hydrostatic testing, cleaning and disinfection of
water services.
Plumbing Code of Australia: Part B2 Heated Water
Services AS/NZS 3500.4-2003 Heated Water Services;
• Section 1.9 Water Temperature
1.9.1 Storage Temperature
1.9.2 Sanitary fixtures delivery temperature
1.9.3 Acceptable solutions for control of delivery
temperatures
• Section 10 Heated Water Services for People
with Disabilities
• Section 11 Testing and Commissioning
installation compliance
Hot Temperature Supply Range
55°C - 85°C
Cold Temperature Supply Range
5°C - 25°C
Adjustable Temperature
35°C - 45°C
Operating Working Pressure
20 - 500* kPa
Maximum Outlet Pressure*
500 kPa
Permitted Supply Pressure Variation^
10%
Operating Thermostatic Temp. Range*
full cold - 45°C
Factory Set Thermostatic Temp. Range
39°C - 41°C
Maximum Thermostatic Temperature
45°C
Minimum Flow Rate
2 L/minute
Maximum Flow Rate
15.5 L/minute
AS 4032.1
WMKA25301
^AS3500.4 clause 1.9.4.2 - The dynamic pressure differential between hot and cold supplies when
mixed at a thermostatic mixing valve shall not exceed 10%.