1. Determine desired location with relation to the
handle height off finished floor. Recommended height
from finished floor to cartridge centre for a standard
installation is 1100mm.
2. Determine box position in relation to wall depth,
considering the thickness of the finished wall. Plastic
box may be cut down smaller if required
SEE IMAGE 9.
3. Mark out fixing point locations while ensuring the box is
level. The spirit level inside the box can be seen through
the top access hole. The mixer must be installed with the
inlets and outlet pointing up, to ensure the front-of-wall
components face the correct direction.
SEE IMAGE 10
4. Secure the Shower Box to the internal cavity within the
wall. The Shower Box can be fixed to a masonry wall or
nogging within a wall frame, by using the fixing lugs on
the side of the box and four suitable screws.
If installing within a frame wall, fit mounting timber in
desired location for box support. 13mm plywood fixed
between two vertical in-wall studs is recommended
Important: The depth of box from finished wall to the
back of the box must be between 77mm – 92mm
5. Remove and keep the 4 screws located on the outer
edge of the in-wall box, remove and keep front box
cover at hand.
6. Purge hot and cold supply lines ensuring all debris has
been cleared. Then, connect water supply to inlet fittings
using 1/2” BSP fittings.
Note: Hot and Cold water connections should use unions or
loose-nut connectors to facilitate future servicing or repairs.
Warning: Heat must not be applied to the inlets and outlet
of the mixer while connected to the shower body, as this
may result in damage to the internal components and void
warranty.
If hot works are required, disconnect the loose
nuts from the body before commencing.
7. Connect mixer outlet to riser leading to shower outlet.
8. Turn ON hot and cold water supplies and check for leaks
in the 1/2” threaded joints.
Important: Maximum Static Pressure for testing and
commissioning purposes is 1000 kPa
9. Ensure Hot and Cold isolation valves are in the closed
position.
SEE IMAGE 10.
Use a 3mm Allen key or flat
head screw driver to rotate the isolation valve so that the
slot within its head is horizontal (closed position).
10. Place the box front cover back over the mixer and fix it
in place using the supplied screws previously removed.
11. The wall is ready to be sheeted. Make sure sheeting is
finished hard up against the protruding section of box.
Box cut-out size: 166 mm wide x 222 mm high
installation instructions
ATM608
IMAGE 10
max 92
min 77
15
IN WALL ADJUSTMENT
TRIM DOWN TO SUIT
AFTER INSTALLATION
ISOLATION VALVE
INSPECTION PORT
STRAINER /
CHECK VALVE
ASSEMBLY
HOT IN
COLD IN
MIXED OUT
WALL DEPTH: Max. 92mm, Min. 77mm
IMAGE 9