AFTER INSTALLING THIS UNIT PLEASE PASS ONTO END USER
DO NOT THROW AWAY
42
11
Setting Values
STEP
NO.
DESCRIPTION
FACTORY
SETTING
excl. Plus
ADJUSTING RANGE
STEP DISPLAY TEXT
+ SYMBOLS
20
Extract fan mode
switching input 1
5
0 (= Extract fan off)
1 (= Absolute min. flow rate 50m
3
/h)
2 (= Flow rate mode 1)
3 (= Flow rate mode 2)
4 (= Flow rate mode 3)
5 (= Multiple switch)
6 (= Maximum flow rate)
7 (= no fan activation)
CN1
21
Selection input 2
1
0 (= normally open contact)
1 (= 0 - 10V input)
2 (= normally closed contact)
3 (= input 2/ bypass open
→
12V;
bypass closed
→
0V)
4 (= input 2/ bypass open
→
0V;
bypass closed
→
12V)
V2
22
Minimum voltage input 2
0,0 V
0,0 Volt - 10,0 Volt
0,5 V
V2 MIN
23
Maximum voltage input 2
10,0 V
0,0 Volt- 10,0 Volt
0,5 V
V2 MAX
24
Conditions
switching input 2
0
0 (off)
1 (on)
2 (= On if conditions bypass open satisfied)
3 (= Bypass control)
4 (= Bedroom valve)
CN2
25
Supply fan mode
switching input 2
5
0 (= Input fan off)
1 (= Absolute min. flow rate 50m
3
/h)
2 (= Flow rate mode 1)
3 (= Flow rate mode 2)
4 (= Flow rate mode 3)
5 (= Multiple switch)
6 (= Maximum flow rate)
7 (= No input fan activation)
CN2
26
Extract fan mode
switching input 2
5
0 (= Extract fan off)
1 (= Absolute min. flow rate 50m
3
/h)
2 (= Flow rate mode 1)
3 (= Flow rate mode 2)
4 (= Flow rate mode 3)
5 (= Multiple switch)
6 (= Maximum flow rate)
7 (= No extract fan activation)
CN2
27
Geo heat exchanger
OFF
OFF (= Valve control geo heat exchanger off)
ON (= Valve control geo heat exchanger on)
EWT
28
Minimum temperature geo heat exchanger
(Below this temperature the valve opens)
5,0 °C
0,0 °C - 10,0 °C
0,5 °C
EWT T-
29
Maximum temperature geo heat exchanger
(Above this temperature the valve opens)
25,0 °C
15,0 °C - 40,0 °C
0,5 °C
EWT T+
STEP
NO.
DESCRIPTION
FACTORY
SETTING
ADJUSTING RANGE
STEP DISPLAY TEXT
+ SYMBOLS
30
RH-sensor
OFF
OFF (= RH-sensor not active)
ON (= RH-sensor active)
31
Sensitivity
RH-sensor
0
+2 most sensitive
+1
→
0 default setting RH-sensor
-1
→
-2 least sensitive
Summary of Contents for energiSava 300