WARNING: Only persons licensed to work with gas piping may make the necessary gas connections to this
appliance.
GAS LINE CONNECTION
•
This stove is equipped with a certified flexible pipe located on the right side of the unit terminating in a
⅜” male NPT fitting. Consult your local authorities codes or the CAN/CGA B 149 (1 or 2) installation code in
O
L
I
T
P
T
P
T
H
TP
T
H
IN
OUT
H
I
L
O
N
OF
O
F
LI
P
T
O
Manifold
Pressure Tap
Inlet
Pressure Tap
Hi/Low
Knob
Pilot Adjustment
Screw
Gas Control
Knob
Figure 48:
Fully Labeled Gas Valve
Canada, or in the USA gas installations follow either local
codes or the current edition of the National Fuel Gas
Code ANSI Z223.1.
•
The efficiency rating of this appliance is a product
thermal efficiency rating determined under continuous
operating conditions and was determined independently
of any installed system.
The appliance and its shutoff valves must be disconnected
from the gas supply piping system during any pressure
testing where the pressure exceeds ½ PSIG (3.45 KPa)
or damage will occur to the valve.
The appliance must be isolated from the gas supply
piping system by closing its individual manual shutoff
valve during any pressure testing of the gas supply piping
system at test pressures equal to or less than ½ psig (3.45 KPa).
Always check for gas leaks with a soap and water solution after completing the required
pressure test.
TO TEST VALVE PRESSURES
The pressure taps are located on the left side of the valve
• Turn set screw 1 turn counter clockwise to loosen,
• Place
5
/
16
” (8 mm) I.D. hose over pressure tap system.
• Check pressures using a manometer.
• When finished, release pressure, remove hose & tighten set screw.
Initial Installation
QUALIFIED INSTALLERS ONLY
Natural Gas
Propane
Main Burner
#39 DMS
#53 DMS
Manifold Pressure
3.8” W.C. / 0.95KPa
11.0” W.C. / 2.7KPa
Min� Manifold Pressure
1.1” W.C. / 0.27KPa
2.7” W.C. / 0.67KPa
Max Supply Pressure
7.0” W.C. / 1.74KPa
13.0” W.C. / 3.28KPa
Min. Supply Pressure
5” W.C. / 1.24KPa
12.0” W.C. / 2.98KPa
Max BTU/hr Input
30,000 BTU/hr (8.80KW)
26,500 BTU/hr (7.76KW)
Min. BTU/hr Input
17,000 BTU/hr (4.98 KW)
14,000 BTU/hr (4.10KW)
Venturi Setting
1
/
16
” min.
3
/
16
” min.
Table 6:
Pressure and BTU Information
NEVER USE AN OPEN FLAME FOR LEAK TESTING�