Enviro Westley Owner'S Manual Download Page 36

GENERAL VENTI NG I NFORMATI ON:

Canadian I nstallations

The venting system must be installed in accordance with the current CSA B149.1 installation code and/or 

local codes having jurisdiction.

U.S.A. I nstallations

The venting system must be installed in accordance with the current National Fuel Gas Code, ANSI Z223.1/

NFPA 54, and/or local codes having jurisdiction. It is strongly recommended to install an approved chimney 

Figure 46: B-Vent Setup

4" (10cm) 

vent

6" (15cm) 

optional 

decorative 

cover

Check vent draft 

at the top row of 

opening.

Figure 47: Draft test place.

liner in an existing brick chimney. This will maximize the potential 

draft of the chimney and lessen the effects of slow chimney start-

up. 

VENTI NG OF A FI REPLACE FI TTED WI TH THE DRAFTHOOD 
ADAPTOR:

Note:

  Please  refer  to  the  chimney  manufacturer’s  installation 

instructions prior to commencing the installation.

 

This unit may 

be vented to an existing masonry chimney, or where no masonry 

chimney is available, an approved “B-vent” chimney, or any other 

approved  constructed  chimney/vent  system  (see  Figure  46).  In 

either case, the fireplace must be connected to the chimney/vent 

using a 4” (10 cm) single wall flexible venting.
When an existing masonry chimney is utilized for the venting, it is 

required the drafthood be connected to an approved 4” (10 cm) 

diameter flexible flue liner running the full height of the chimney. 

In many jurisdictions this flue liner may be mandatory. A minimum 

of 6” (15 cm) must be maintained between the venting and any 

combustibles when using 4” (10 cm) single wall flexible venting.

Venting  Restrictions: 

The  vent  lengths  below  are  measured 

from the floor to the top of the flex venting and cannot run in the 

horizontal dimension other than passing through a wall thimble 

into existing masonary.

  - 

Minimum: 10 ft (3.05m)

  - Maximum: 30 ft (9.14m)

SPI LLAGE TEST:

A spillage test must be performed prior to leaving the installed 

fireplace  with  the  customer.  Perform  this  test  in  the  following 

manner:

1. Close all windows and doors in the room.
2. Start all exhaust fans in the house and the furnace blower.
3. Light the fireplace and set to maximum flame adjustment.
4. After a minimum of 10 minutes operation, test the chimney draft 

with a smoke match at the top row of the pattern to confirm that 

there is adequate draft or ‘pull’ at the openings around the body 

of the Drafthood Adaptor, as shown in Figure 47.

Initial Installation

36

Summary of Contents for Westley

Page 1: ...injury or loss of life Installation and service must be performed by a qualified installer service agency or the gas supplier Version Fran aise www enviro com fr html W A R R A N T Y R E G I S T R A T...

Page 2: ...plumber or gas fitter when installed within the Commonwealth of Massachusetts Other Massachusetts code requirements Flexible connector must not be longer than 36in a shut off valve must be installed o...

Page 3: ...e performed by a qualified installer service agency or gas supplier This installation must conform to local codes or in the absence of local codes with the National Fuel Gas Code ANSI Z223 1 NFPA 54 o...

Page 4: ...e Glass 15 Cleaning the Firebox 15 Replacing the Glass 15 Flashout Guard 15 Cast Door Removal 16 Glass Door Removal 16 Burner Removal 17 Fuel Conversion 18 Initial Installation 20 Preparation for Inst...

Page 5: ...HEATERS CSA 2 17 GAS FIRED APPLIANCES FOR HIGH ALTITUDES CSA P 4 1 TESTING METHOD FOR MEASURING ANNUAL FIREPLACE EFFICIENCY This ENVIRO Westley Fireplace Has been certified for use with either natural...

Page 6: ...Dimensions Rating LabeL Lighting instRuctions Location The rating label and lighting instructions are located on a plate hanging on the back of of the unit 27 1 2 69 9 cm 25 15 16 65 9 cm 19 9 16 49 7...

Page 7: ...pliance and to replace any part of the control system and any gas control which has been under water OPERATING INSTRUCTIONS 1 STOP Read the safety information above on this label 2 Read the owner s ma...

Page 8: ...If the shutter is opened or closed all the way and the correct flames cannot be attained turn off the gas and contact the dealer Warning Incorrect shutter adjustment may lead to improper combustion wh...

Page 9: ...gure 4 The Transmitter is powered by three 3 AAA type batteries A Mode Key is provided to Index between the features and a Thermostat Key is used to turn on off or index through Thermostat functions F...

Page 10: ...the particular Proflame 2 system configuration The IFC has a red reset button at the front right corner that is used is to synchronize the Transmitter when using the for the first time or after the b...

Page 11: ...display will show all active Icons on the screen A single beep from the IFC will confirm reception of the command and will commence to first ignite the pilot light followed by the main burner This sh...

Page 12: ...e difference between the set point temperature and the actual room temperatures As the room temperature gets closer to the set point the Smart Function will modulate the flame down To activate this fu...

Page 13: ...ure 4 to index to the fan control icon Figure 13 Use the UP DOWN arrow keys to turn on off or adjust the fan speed Figure 13 A single beep from the IFC will confirm the command has been received Figur...

Page 14: ...the number of changes to the room thermostat set point etc When the Transmitter batteries are low a Bettery Icon will appear on the LCD display of the Transmitter see Figure 17 before all battery pow...

Page 15: ...Ion log set InstallatIon section If any logs are damaged contact your nearest ENVIRO dealer RepLacing the gLass The glass in the fireplace is a high temperature ceramic If the glass is damaged in any...

Page 16: ...hown in Figure 22 To replace the glass door simply reverse the above procedure Warning Do not touch or attempt to remove the glass door if the fireplace is not completely cold WARNING Never operate th...

Page 17: ...ear burner screws using a T20 screwdriver 5 Unsrew the front burner bolt located in the middle of the front row of burner holes using a 5 32 Allen head screwdriver or wrench 6 Slide the burner to the...

Page 18: ...on kit If any parts have been damaged or are missing contact your dealer distributor or courier company to have them replaced before starting this installation Maintenance And Service Conversion Kit I...

Page 19: ...ved Teflon tape NEVER USE AN OPEN FLAME WHEN TESTING FOR LEAKS 12 Relight the pilot and confirm the flame properly covers the flame sensor see Figure 27 Should the pilot require adjustment turn the ad...

Page 20: ...ll or ceiling joist Check stove and flue system clearance requirements Locate the stove where it can be accessed by a gas supply line Locate the stove in a large and open room that is centrally locate...

Page 21: ...not be recessed into a wall or siding WARNING This gas appliance must not be connected to a chimney flue serving a separate solid burning appliances Figure 29 Vent Framing For Wall or Ceiling DiRect v...

Page 22: ...6DVA FF 4F Flat flashing 46DVA VCH SVT High wind vertical termination 4DHCS 4DT HC 46DVA HC HT High wind horizontal termination 4DT HKA 4DT HKB 46DVA KHC 4HTK Horizontal termination kit 4DT CCKA 46DVA...

Page 23: ...y be opened C 12 in 30 cm Clearance from permanently closed window to prevent condensation D 24 in 60 cm Vertical clearance to ventilated soffit located above the terminal within a horizontal distance...

Page 24: ...E until the required setting is inline with the finger catch Refer to the following Allowable Venting Configuration graphs for the required restrictor setting The proper setting is crucial for an effi...

Page 25: ...Length Approved through wall thimble 2 61 cm length NG 3 91 cm length LP 12 30 5 cm Maximum Horizontal Length 5 12 7 cm Minimum Rear Clearance Exterior Wall 55 5 141 cm Minimum Height NG 67 5 171 cm...

Page 26: ...shown in Figures 35 36 In addition to what is shown if a 90 elbow is used in the horizontal plane 3 ft 91 4cm must be subtracted from the allowable horizontal run for each 45 elbow 1 5ft 45 7cm must...

Page 27: ...17 18 19 20 21 22 23 24 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 HORIZONTAL RUN ft VERTICAL RISE Restrictor Setting 1 No Restriction 0 INSTALLATION PROHIBITED Min 3 Section Required Propane...

Page 28: ...TAL RUN ft VERTICAL RISE 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 INSTALLATION PROHIBITED Restrictor Setting 1 Restrictor Setting 3 Restrictor Setting 2 INSTALLATION PROHIBITED Natural Gas...

Page 29: ...2 1 HORIZONTAL RUN ft VERTICAL RISE 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 INSTALLATION PROHIBITED Restrictor Setting 1 Restrictor Setting 2 INSTALLATION PROHIBITED Propane LP Initial I...

Page 30: ...he air gap prevents excessive heat from possibly melting the vinyl siding 5 Horizontal pipes must be supported every 3 feet 914 mm Plumber s all round strap will suffice 6 When running horizontal pipe...

Page 31: ...he vent termination should be pointing up Run a bead of non hardening mastic around the edges of the vent cap to make a seal with the wall Ensure the proper clearances to combustibles have been mainta...

Page 32: ...the base of the flashing to the roof with roofing nails Use a non hardening sealant between the uphill edge of the flashing and the roof Insure the roofing material overlaps the top edge of the flashi...

Page 33: ...oors see Figure 41 The opening should be framed to 10 254 mm x 10 254 mm inside dimensions in the same manner as shown in Figure 29 4 Any occupied areas above the first floor including closets and sto...

Page 34: ...adaptor so the wires exit to the rear of the fireplace Slide the Drafthood Adaptor over the outlet pipe of the fireplace until the bottom of the adaptor collar stops on the top of the outlet The Draft...

Page 35: ...removed from the Drafthood Adaptor for this modification Figure 43 Step 2 Strip off approx 1 4 of insulation from the wire ends Step 3 Remove the ON OFF terminal block from the X4 port on the IFC Figu...

Page 36: ...must be connected to the chimney vent using a 4 10 cm single wall flexible venting When an existing masonry chimney is utilized for the venting it is required the drafthood be connected to an approved...

Page 37: ...48 4 Remove and replace the spill switch with a 50 885 Spill Switch Assembly using a T 20 torx type driver 5 Follow the reverse of the previous steps OPTI ONAL FI NI SHI NG In installations where the...

Page 38: ...rom the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than psig 3 45 KPa Always...

Page 39: ...tion against shock hazard and should be plugged directly into a properly grounded three prong outlet DO NOT cut or remove the grounding prong from this plug CAUTI ON When servicing controls label all...

Page 40: ...ht side at the rear of the firebox Slide the log left until it contacts the finger stop next to the pilot shield Figure 51 Note Ensure the metal air scoop is installed on the burner pan before proceed...

Page 41: ...rovided coals on the burner pan in front of the air holes but do not block them figure 56 Using the supplied brush evenly spread the ember wool and Embaglow on top of the burner pan as shown Figure 57...

Page 42: ...t for it to cool down Then remove the glass and make sure none of the burner ports are blocked Figure 62 Proper Burn and Flame Maintenance Once a year the logs should be removed and checked for deteri...

Page 43: ...retaining bolts Figure 63 using a 1 4 socket and remove the damaged screen while noting the orientation Install the new screen 50 3715 by simply re installing the retaining bolts Re install the cast...

Page 44: ...blink one 1 time in intervals 3 Parasitic Pilot Flame the LED indicator will blink two 2 times in intervals 4 System Lock out the LED indicator will blink three 3 times in intervals Additional Ignitio...

Page 45: ...rifice Pilot will not remain lit 7 Day Shutdown The pilot has been in operation for 7 continuous days without main burner operation Turn fireplace ON to reset pilot timer Problem with Flame Sensor cir...

Page 46: ...temperature Flame lifting Leak in vent pipe Check for leaks in vent connections Improper vent configuration Check vent configuration with manual Terminal may be re circulating flue gases Check to see...

Page 47: ...Assembly 50 3730 10 Burner Mounts set of 4 50 3731 11 Convection Fan only EC 069 12 Heyco Strain Relief EC 044 13 Domestic Power Cord 115v EC 042 14 Side Door Complete 50 3734 15 Side Door Glass w Gas...

Page 48: ...Parts List 21 1 2 12 13 15 14 16 7 6 5 4 3 9 8 11 20 17 18 19 10 48...

Page 49: ...19 Cast Front Antique Bronze 50 3720 24 Cast Skirt Painted 50 3721 Cast Skirt Antique Bronze 50 3722 25 Cast Right Side Painted 50 3723 Cast Right Side Antique Bronze 50 3724 26 Cast Left Side Painted...

Page 50: ...Notes 50...

Page 51: ...ety screen mesh Exclusions An expanded list of exclusions is available at www enviro com help warranty html This warranty does not cover Damage as a result of improper usage or abuse Damage caused fro...

Page 52: ..._______________________________ MODEL ___________________________________ SERIAL NUMBER ___________________________ DATE OF PURCHASE _____________ dd mm yyyy DATE OF INSTALLATION ___________ dd mm yyy...

Reviews: