Maintenance And Service
8. Reinstall the air diverters, burner tube, grate, and the ceramic log set as indicated in this manual.
9. Reconnect the main gas line if it was disconnected and open the shut-off valve at the gas line to the
unit.
10. Use a small brush to apply a warm soapy water solution to all gas connections (use a half dish soap
and half warm water). If a gas leak is present, bubbling will occur. Gas leaks can be repaired by
using an approved pipe thread sealant or approved Teflon tape. NEVER USE AN OPEN FLAME WHEN
TESTING FOR LEAKS.
11. Reconnect the electrical power to the unit.
12. Relight the pilot and confirm the flame properly covers both the thermocouple and thermopile (see
Figure 4, page 8)
.
Should the pilot require adjustment, turn the adjustment screw (figure 30, page
29) clockwise to decrease or counterclockwise to increase until the correct flame is achieved.
13.
Relight the main burner in both the “HI” and “LO” positions to verify proper burner ignition, operation
and proper flame appearance. Confirm the inlet and manifold pressures are within the acceptable
ranges as directed in section
I
ntIal
I
ntallatIon
- G
as
l
Ine
c
onnectIon
anD
t
estInG
.
If the Q2 has
Figure D. O-ring on valve screw.
been installed at an altitude higher than 2000ft (610m) it is required to de-rate the unit accordingly:
In the USA:
The appliance may be installed at higher altitudes. Please refer to your American Gas
Association guidelines which state: the sea level rated input of Gas Designed Appliances installed at
elevations above 2000 (610 m) feet is to be reduced 4% for each 1000 feet (305 m) above sea level.
Refer also to local authorities or codes which have jurisdiction in your area regarding the de-rate
guidelines.
In Canada
: When the appliance is installed at elevations above 4500 feet (1372 m), the certified high
altitude rating shall be reduced at the rate of 4% for each additional 1000 feet (305 m).
14. MAKE SURE that the conversion label is installed on or close to the rating label to signify that the
unit has been converted to a different fuel type.
g) Re-attach the black protection
cap that was removed in step
a (Figure A`).
Page 14