Connecting the external indicator light housing
The LYNX 3400's indicator light housing has red and green lights. It is
supplied with a 3X1.5mm² U1000RO2V type cable. Position the indicator light
with the cable gland facing downwards.
Connect the J9 terminal block as follows:
Te: Brown wire
Terminal V: Black wire
Terminal R: Grey wire (or blue)
+ V R
Connecting to remote indication
The connection is made using a 4X1.5mm² U1000RO2V type cable (not
supplied). An equipment fault may be actuated by the detector in
response to:
- A need to replace the battery or batteries when the original battery
becomes flat after 7.5 years of use
- An anomaly affecting the alternative auxiliary power supply
- An anomaly affecting the electronics
Connect the J5 terminal block (removable and screwed-in) as follows:
Terminals NC: Not connected
Terminal R: Red fault
Terminal V: Green fault
Terminal DE: Equipment fault
Terminal C: Common
NCNC R V DE C
2
.
Inst
a
ll
a
ti
on