3.2 List of commissioning operations
Configuration fault detection sensitivity
The LYNX 3400s have two detection levels labeled "Jeu 1" and "Jeu 2" (Game 1
and 2).
Game 1 corresponds to the greater sensitivity of the earth fault detection, this
position is used preferentially.
The game position 2 is intended for special cases including that of detectors
complementing the departure equipment comprising a majority of directional
detectors of older generation (prior to 2009).
To validate the parameter set, set IN16 to GAME 1 or GAME 2 and then press
BP1 to memorize the position of the inverter.
IN 16 - GAME 2
IN 16 - GAME 1
Game 1: factory setting position
Configuring the network's MV voltage
To take into account the network's MV voltage, the configuration of the voltage is
carried out by the inverter ST2.
S
T
2
Medium voltage 15 kV
Medium voltage 20 kV
20 kV: factory setting position