12
LYNX 3400
manual
72789_b
/
NX2009363
Each core is mounted on an underground cable phase, with the green
side facing towards the unit's busbar
.
It is centered and attached to the cable using 3 self-centering rubber
bosses.
The screened braid for each phase has to be created by an insulated
conductor and passed inside the corresponding core.
The wires for each core are connected using a coded 2-contact MATE-N-
LOCK connector.
A 4x1.5mm² U1000RO2V type cable equipped with female MATE-N-
LOCK connectors is supplied for connecting cores to the LYNX 3400's J2
terminal block.
Insert the stripped end with end sleeves into the LYNX's
cable grommet.
Connect the J2 terminal block as follows:
l1 l2 l3 C NC
Terminal I1: Brown wire
Terminal I2: Black wire
Terminal I3: Grey wire
Terminal C: Blue wire (common)
Terminal NC: Not connected