EEP
The EEP register determines the EnOcean Equipment Profile (EEP) used by STM 550x for
the transmission of data telegrams. Figure 34 below shows the structure of the EEP regis-
ter.
EEP (Default: 0x00)
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
RFU
EEP
Figure 34
–
EEP register
The encoding used by the SIZE bit field is shown in Table 14 below.
EEP
EnOcean Equipment Profile
0b0000 (Default)
D2-14-41
0b0001
D2-14-40
0b0010
A5-02-05
0b0011
A5-04-03
0b0100
A5-06-03
0b0101
A5-06-02
0b0110
D5-00-01
0b0111
A5-14-05
0b1000
A5-04-01
Others
Reserved, do not use