USER MANUAL
STM 550X / EMSIX
–
ENOCEAN MULTI-SENSOR
© 2020 EnOcean | www.enocean.com F-710-017, V1.0
STM 550x / EMSIx User Manual | v1.0 | February 2020 | Page 56/79
8.5.12
STANDARD_TX_INTERVAL
STM 550x uses a standard reporting interval which can be automatically adjusted based on
sensor readings as described in chapter 2.4. The standard reporting interval is set by the
register STANDARD_TX_INTERVAL shown in Figure 38 below.
STANDARD_TX_INTERVAL (Default: 0x003C)
Bit 15
Bit 14
…
Bit 1
Bit 0
STANDARD INTERVAL
Figure 38
–
STANDARD_TX_INTERVAL register
The encoding used by the STANDARD INTERVAL bit field is shown in Table 18 below.
STANDARD INTERVAL
Standard Reporting Interval
0x0000, 0x0001, 0x0002
Not supported (Do not use)
0x0003
3 seconds (minimum setting)
…
…
0x003C (Default)
60 seconds (default setting)
…
…
0xFFFF
65535 seconds (maximum setting)
Table 18
–
STANDARD INTERVAL bit field encoding