Operating Mode 

 

The occupancy sensor is in operating mode after it has successfully been initialized (as 
described above) and for as long as sufficient power (generated from ambient light and 
stored within the internal energy store) is available. 

 

Linking (learning in) the occupancy sensor 

Pressing the menu button in normal operating mode will transmit a link (learn, teach-in) 
telegram.  The green (link) LED will blink to indicate that a link telegram has been sent. 

This link telegram identifies the ID of the occupancy sensor and the EnOcean Equipment 
Profile (EEP) used by the sensor (EEP A5-07-01). Based on this information, the receiver 
can properly react to subsequent data telegrams from the occupancy sensor 

 

Occupancy Detection and Transmission 

If the occupancy sensor detects occupancy for the first time (after a period without 
occupancy) then it will immediately transmit of a data telegram indicating the detected 
occupancy. 

After that immediate initial transmission, the sensor will continue to transmit data 
telegrams indicating the detected occupancy every two minutes for as long as occupancy 
is detected. 

 

Unoccupied Transmission 

If - after a period with detected occupancy - the sensor does not detect occupancy 
anymore for 10 minutes then it will send a data telegram indicating that no occupancy is 
detected.  

If the sensor still does not detect occupancy after another 20 minutes, a second data 
telegram will be transmitted indicating that no occupancy is detected. After that, no 
additional data telegrams will be sent to indicate that no occupancy is detected. 

 

 

Summary of Contents for EOSCA

Page 1: ...EnOcean Occupancy Sensor Operational Description Revision 1 2 June 02 2016...

Page 2: ...2 REVISION HISTORY Rev Date Revision Description Revised By 1 0 3 22 2013 First Revision BE 1 1 5 22 2013 Editorial Changes BE 1 2 06 02 2016 Updated bit field description to ensure EEP compliance MKA...

Page 3: ...3 Table of Contents Introduction 4 User Interface 4 Startup Mode 4 Operating Mode 5 Configuration Mode 9 Telegram Types and Data Transmitted 11...

Page 4: ...rking The sensors include a walk test mode to validate the sensors ability to detect occupancy and a light level test to determine the suitability of an installation location User Interface The user i...

Page 5: ...om the occupancy sensor Occupancy Detection and Transmission If the occupancy sensor detects occupancy for the first time after a period without occupancy then it will immediately transmit of a data t...

Page 6: ...corresponding data telegram has been sent Heartbeat transmission functionality is optional and disabled by default Enabling this functionality will reduce the operation time of the sensor without powe...

Page 7: ...LEDs are blinking and walk test mode will be entered The occupancy sensor will now transmit a data telegram indicating the occupancy sensor every two seconds If occupancy is detected then the red LED...

Page 8: ...and lens LEDs will blink a certain amount of times to indicate the amount of current being harvested from the solar panel Every second a pattern of 0 5 blinks will be shown The number of blinks corre...

Page 9: ...he red LED will blink once immediately after holding the menu button and configuration mode cannot be entered Feedback about the updated status is given after releasing the menu button Three blinks fr...

Page 10: ...ng as follows LED blink on motion transmission enabled 3 blinks from green LED LED blink on motion transmission disabled 3 blinks from red LED Heartbeat Transmission To enable disable heartbeat transm...

Page 11: ...Byte 2 0x08 Data Byte 1 0x0B Data Byte 0 0x87 Data Telegram Occupied Unoccupied and Heartbeat Telegram The occupancy sensor transmits data telegrams according to EEP A5 07 01 Unused data fields are se...

Reviews: