Walk Test Mode 

In walk test mode, the red LED and the lens LED will blink when motion is detected.  
Occupied and unoccupied telegrams are sent with a motion lockout and heartbeat of two 
seconds while in walk test mode. 

To enter walk test mode, press and hold the set button  when the sensor is in normal 
operating mode.  

After five seconds of holding down the set button, the red LED and the lens LED will 
begin to blink.  Release the set button while these LEDs are blinking and walk test mode 
will be entered.   

The occupancy sensor will now transmit a data telegram indicating the occupancy sensor 
every two seconds. If occupancy is detected then the red LED underneath the PIR lens 
will blink to provide visual feedback. 

After 180 seconds of entering walk test mode, it will automatically timeout and return to 
normal operating mode.  Pressing  either the teach button or the test button will force 
walk test mode to exit. 

Walk test mode is only possible if the energy store is charged above 2.8V.  Otherwise, 
the red LED will blink once immediately after holding the set button and walk test mode 
cannot be entered.   

 

 

 

Summary of Contents for EOSCA

Page 1: ...EnOcean Occupancy Sensor Operational Description Revision 1 2 June 02 2016...

Page 2: ...2 REVISION HISTORY Rev Date Revision Description Revised By 1 0 3 22 2013 First Revision BE 1 1 5 22 2013 Editorial Changes BE 1 2 06 02 2016 Updated bit field description to ensure EEP compliance MKA...

Page 3: ...3 Table of Contents Introduction 4 User Interface 4 Startup Mode 4 Operating Mode 5 Configuration Mode 9 Telegram Types and Data Transmitted 11...

Page 4: ...rking The sensors include a walk test mode to validate the sensors ability to detect occupancy and a light level test to determine the suitability of an installation location User Interface The user i...

Page 5: ...om the occupancy sensor Occupancy Detection and Transmission If the occupancy sensor detects occupancy for the first time after a period without occupancy then it will immediately transmit of a data t...

Page 6: ...corresponding data telegram has been sent Heartbeat transmission functionality is optional and disabled by default Enabling this functionality will reduce the operation time of the sensor without powe...

Page 7: ...LEDs are blinking and walk test mode will be entered The occupancy sensor will now transmit a data telegram indicating the occupancy sensor every two seconds If occupancy is detected then the red LED...

Page 8: ...and lens LEDs will blink a certain amount of times to indicate the amount of current being harvested from the solar panel Every second a pattern of 0 5 blinks will be shown The number of blinks corre...

Page 9: ...he red LED will blink once immediately after holding the menu button and configuration mode cannot be entered Feedback about the updated status is given after releasing the menu button Three blinks fr...

Page 10: ...ng as follows LED blink on motion transmission enabled 3 blinks from green LED LED blink on motion transmission disabled 3 blinks from red LED Heartbeat Transmission To enable disable heartbeat transm...

Page 11: ...Byte 2 0x08 Data Byte 1 0x0B Data Byte 0 0x87 Data Telegram Occupied Unoccupied and Heartbeat Telegram The occupancy sensor transmits data telegrams according to EEP A5 07 01 Unused data fields are se...

Reviews: