Solution 1.6 Installation and Operation Manual
35
8.2.2 Factory-built Metal Chimneys in
mobile homes
For use in a mobile home, this stove is to be
connected to a 6” in diameter double wall factory
built chimney conforming to CAN/UCL-S629,
Standards for 650°C Factory-built chimney. The
total length of the flue system should be at least
12 feet including elbows, from the top of the stove.
To maintain an effective vapour barrier, insulation
and waterproof at the chimney and outside flue
pipe, install a mobile home roof flashing and seal it
with silicone.
8.2.3 Masonry Chimneys
The stove may also be connected to a masonry
chimney, provided the chimney complies with the
construction rules found in the building code
enforced locally. The chimney must have either a
clay liner or a suitably listed stainless steel liner. If
the masonry chimney has a square or rectangular
liner that is larger in cross sectional area than a
round 6” flue, it should be relined with a suitably
listed 6” stainless steel liner. Do not downsize the
flue to less than 6” unless the venting system is
straight and exceeds 25 feet in height. When
passing through a combustible wall, the use of a
factory built thimble is required.
Summary of Contents for Solution 1.6 AGENCY PHASE II CERTIFIED WOOD
Page 8: ...8 Solution 1 6 Installation and Operation Manual ...
Page 32: ...32 Solution 1 6 Installation and Operation Manual Clearances for shield construction ...
Page 49: ...Solution 1 6 Installation and Operation Manual 49 Floor installation ...
Page 55: ...Solution 1 6 Installation and Operation Manual 55 Appendix 9 Exploded Diagram and Parts List ...