22
3940011 12.12
7. Troubleshooting
Problem
Possible Cause
Action
EBC30 Display
A1 Draft Exhaust (
Insufficient
Draft Pressure)
1. Mechanical or Electrical Failure
2. Blocked Chimney
3. Faulty XTP2 Sensor
1. Check wiring
2. Check for blockages in chimney
3. Check for problems with the XTP2
A3 Power Fault
Power Fault
1. Check power supply
A4 XTP-Exhaust (
Signal
Disconnected from XTP)
1. Faulty Wiring
2. Faulty XTP2 Sensor
3. Faulty Control
1. Check XTP2 Connections
2. Contact ENERVEX’s technical department
Yellow light (UP) is lit
continuously
1. Faulty Wiring
2. Inadequate Fan Capacity
3. Clogged Stack Probe or Tube
1. Check wiring to and from control.
2. Check for blockages in stack probe or tubing
3. Contact ENERVEX’s technical department
Yellow light (DOWN) is lit
continuously
1. Control Malfunction
1. If a Triac Board is installed this is an indication that
the neutral connection is shared with other equipment.
It must be a dedicated line between the control and
the fan.
RSV Fan
The fan is not operating.
1. No power to the fan.
1. Check the power supply wires in the junction box
by the fan.
2. Check the circuit breaker.
3. Check that the fan is actually turned ON.
The fan is not running at full
speed and/or is humming.
1. The capacitor is improperly
connected or not connected at all
(single-phase fans only).
1. Check the connections inside the junction box.
The capacitor must be installed according to wiring
diagram.
The fan is rotating backwards
(RSV 400/450 only).
1. Phase sequence in the power to
the fan is reversed.
1. Swap two phases in the junction box.
The fan is vibrating vigorously. 1. The motor shaft is damaged.
1. Turn the power off immediately. Open the fan
and check if the shaft is straight. If not, contact
ENERVEX.
The fan is noisy.
1. A transportation device has
not been removed.
2. Foreign matter is stuck in the
fan.
3. A ball bearing is damaged.
1. Remove the transportation device.
2. Turn off the power and remove the foreign article.
3. Turn off the power. Wait for the motor to stop
revolving. Spin the wheel and listen for any grinding
noise from the motor. If necessary, replace bearing.
The fan stops in the middle of
a firing cycle.
1. The motor is overheating.
1. Check the flue gas temperature below the fan.
The temperature should not exceed 400°F during
continuous operation. Call ENERVEX.
ISOKERN IBV Fireplace*
Gas log burner goes out
1. Pilot too small to keep
thermocouple hot
2. Low gas pressure; pilot fades
1. Locate the screw on the burner assembly and turn
CCW to increase pilot flame
2. Contact your ISOKERN representative
Pilot will not reamain lit
1. Short in mili-volt circuit
1. Check for loose connections in the safety circuit
2. Make sure the length of wire in the safety circuit
does not exceed 10 feet
*See the ISOKERN manual for additional troubleshooting of the IBV fireplaces