background image

10

3940011   12.12

3.1 General

The code requirements for a mechanical draft system are different than those for a gravity venting system  

 

used with gas applications. Generally, the mechanical draft system must be installed a minimum of 3 feet   

 

away from any forced air inlet located within 10 feet and a minimum of 4 feet away from any door   

 

 

or window. For complete information, consult ENERVEX or your local building codes.

 

Installation must be in accordance with these instructions and all local codes, or in their 

absence, the National Fuel Gas Code, NFPA 54/ANSI 223.1.

 

This installation manual is for the ENERVEX venting system and assumes that the ISOKERN fireplaces 

have already been installed.  Installion of the ISOKERN fireplaces, the gas logs and the pilot assembly 

should be performed by a qualified ISOKERN technician or a certified gas service agent or supplier.  If you 

have any questions regarding installation of these components, consult the ISOKERN installation manual.

Important information about ISOKERN IBV fireplaces

•  ISOKERN IBV model fireplaces are designed for use with standard B-vent. ENERVEX does not recommend    

 

installing more than 100’ of B-vent in the vertical run of the system.  If the common vertical vent is over  

 

 

100’, you must use a listed pressure stack or another alternative.  For information on circumstances where it is  

 

appropriate to use B-vent in a vertical common vent greater than 100’, contact ENERVEX.    

•  If temperatures in the firebox exceed 160° F, the ISOKERN IBV fireplace has a thermal limit switch that  

 

 

opens the safety circuit and closes the gas valve.  

DO NOT mount the transducer inside an airtight enclosure.  It uses the room pressure 

as reference pressure.

!

Adequate intake air must be provided for combustion of the fireplaces; otherwise, 

improper operation and inadequate venting of deadly flue gases may result.

   3.  SYSTEM INSTALLATION & SET UP GUIDELINES

Summary of Contents for Multiple Fireplace

Page 1: ...923 info enervex com www enervex com Job Name Installer Installation Date SYSTEM COMPONENT DESCRIPTION DIMENSIONS CAPACITIES SYSTEM INSTALLATION SET UP GUIDELINES ELECTRICAL CONNECTIONS INSTALLATIONS...

Page 2: ...u have questions contact the manufacturer at the address or telephone number listed on the front of the manual 2 Before servicing or cleaning the unit switch off at service panel and lock service pane...

Page 3: ...ernal pressure transducer that monitors pressure in the vertical common vent The transducer converts measured pressure into a corresponding voltage This voltage is relayed to the control to modulate t...

Page 4: ...damper and actuator with end switch ISOKERN fireplace Fig 1 1 3 System Description During operation the EBC 30 maintains a constant negative pressure in the vertical common vent and fireplace connect...

Page 5: ...20 to 50 Range of Operation inWC Pa 0 0 6 0 150 Tolerance inWC Pa 0 01 3 10 Control Signal mA max 10 Control Relay Max 120 VAC 8A Output VAC 10 120 VDC 0 10 Dimensions A in mm 14 65 372 B in mm 11 03...

Page 6: ...y FPM 2 9 x CFM 1 9 x CFM 1 2 x CFM 1 03 x CFM 1 03 x CFM Voltage V AC 1x120 3x208 240 3x400 RPM 1600 1720 Amps A 1 4 2 9 5 8 3 5 2 1 6 5 3 8 Power Ratings kW 0 10 0 16 0 35 0 75 1 5 HP 0 15 0 2 0 5 1...

Page 7: ...Output VDC 0 10 Operating Temperature F C 0 to 160 18 to 71 Accuracy inWC Pa 0 08 Dimensions D in mm 3 70 94 E in mm 5 12 130 F in mm 6 18 157 G in mm 3 13 80 Weight lbs kg 6 3 2 3 XTP Sensor 2 4 Sta...

Page 8: ...54 305 356 406 457 508 B in 5 88 7 88 9 88 11 788 13 88 15 88 17 88 19 88 mm 146 197 248 298 349 400 451 502 Model ADM 22 ADM 24 ADM 26 ADM 28 ADM 30 ADM 32 ADM 34 ADM 36 Dimensions A in 22 24 26 28 3...

Page 9: ...0 Max Inlet Supply Pressure LP in WC Pa 13 3250 Dimensions A in mm 43 0 1092 53 0 1346 B in mm 25 25 641 25 25 641 C in mm 70 5 1791 70 5 1791 D in mm 31 75 806 31 75 806 E in mm 37 0 940 47 25 1200 F...

Page 10: ...service agent or supplier If you have any questions regarding installation of these components consult the ISOKERN installation manual Important information about ISOKERN IBV fireplaces ISOKERN IBV mo...

Page 11: ...another bead of silicone around the perimiter of the fan Do NOT block the 4 drain holes located on each side of the base To mount the fan on a SCA 1 Insert the SCA into the vent see Fig 4 If necessary...

Page 12: ...XTP2 Sensor To install the XTP2 Sensor 1 Mount the sensor indoors within 300 feet 91 meters of the EBC 30 and 6 feet 1 meter of the stack probe Note You may increase the distance between the stack pr...

Page 13: ...using the silicone tube 5 Verify the tube is connected to the proper transducer port See Fig 8 3 4 ADM Installation Place an access panel in the wall near the location of the ADM The panel should be l...

Page 14: ...igned for 1x120VAC power supply only Fan output is regulating on the neutral side and cannot be connected to other circuits The wiring in is manual is in accordance with NFPA 70 All field wiring must...

Page 15: ...ircuit closes when the damper is open and allows operation of the fireplace If the damper closes the circuit opens and shuts off the gas flow to the fireplace a Connecting to a Manual or Remote Igniti...

Page 16: ...of the transformer in the electronic ignition box Connect the endswitches to the mili volt circuit as shown in Fig 12 4 3 XTP2 Connection Wire the XTP2 Sensor in exhaust mode to terminals 40 41 and 39...

Page 17: ...he fan connects to the VFD as shown DO NOT connect the fan directly to the EBC 30 control The VFD runs off a 0 10 VDC signal from the EBC 30 See Fig 12 and 13 for connection detail NOTE Before wiring...

Page 18: ...ac board is connected via a multi plug Verify this connection is tight before connecting the fan Terminal descriptions of the triac board are shown in Fig 15 Connect the fan as shown in Fig 16 NOTE Fa...

Page 19: ...int The draft effects of the chimney fan will decrease as the fireplaces become further away and the set point must be set to ensure a constant negative pressure at the furthest fireplace from the fan...

Page 20: ...pers farthest from the fireplace will be fully open to 90 To set the damper positions 1 Begin with the fireplace closest to the fan 2 All dampers should be closed except for the one being set 3 Set th...

Page 21: ...t prevents the fireplace from operating when the damper is closed 5 At the same time the damper opens the XTP2 senses the rise in pressure and sends a signal to the control to increase the fan speed u...

Page 22: ...only 1 Check the connections inside the junction box The capacitor must be installed according to wiring diagram The fan is rotating backwards RSV 400 450 only 1 Phase sequence in the power to the fan...

Page 23: ...ENERVEX Inc 1685 Bluegrass Lakes Pkwy Alpharetta GA 30004 P 770 587 3238 F 770 587 4731 T 800 255 2923 info enervex com www enervex com 3940011 12 12...

Reviews: