Enertech WS036 Installation & Operation Manual Download Page 31

Enertech Global, LLC

31

WS Rev. E Models

Installation and Operations Manual

Troubleshooting Tips

A: UNIT WILL NOT START IN EITHER CYCLE

Thermostat

Set thermostat on heating and highest temperature setting. Unit should run. Set thermostat on cooling and lowest 

temperature setting. Unit should run. Set fan to On position. Fan should run. If unit does not run in any position, 

disconnect wires at heat pump terminal block and jump R, G, Y. Unit should run in heating. If unit runs, replace 

thermostat with correct thermostat only.

Loose or Broken Wires

Tighten or replace wires.

Blown Fuse/

Check fuse size, replace fuse or reset circuit breaker.

Check low voltage circuit breaker.

Tripped Circuit Breakers

Check fuse size, replace fuse or reset circuit breaker.

Low Voltage Circuit

Check 24 volt transformer. If burned out or less than 24 volt, replace. Before replacing, verify tap setting and correct 

if necessary. 

B: BLOWER RUNS BUT COMPRESSOR WILL NOT START (COMPRESSOR OVERLOAD, BAD CAPACITOR, HP FAULT)

Logic Board

Check if status light is on and logic board is working properly. Check fault lights. See LED Identification chart in 

Controls Section

Defective Sensors

Check status/fault lights. Sensor is out of normal range for resistance values, open, or shorted. Compare sensor 

resistance values with the charted resistance in Controls Section 

Defective Capacitor

Check capacitor. If defective, replace.

Failed Compressor

See charts M and N for compressor diagnostic. If compressor still doesn’t run, replace it.

Low Pressure Switch 

Low refrigerant charge. Check for pressure. Check for leaks. 

C: BLOWER RUNS BUT COMPRESSOR SHORT CYCLES OR DOES NOT RUN

Wiring

Loose or broken wires. Tighten or replace wires. See A: Unit will not start in either cycle.

Blown Fuse

Check fuse size. Check unit nameplate for correct sizing. Replace fuse or reset circuit breaker.

Check low voltage circuit breaker.

Temporarily bypass flow switch for a couple seconds. If compressor runs properly, check switch. If defective, replace. 

If switch is not defective, check for air in loop system. Make sure loop system is properly purged. Verify flow rate 

before changing switch. . 

Defective Sensors

Check status/fault lights. Sensor is out of normal range for resistance values, open, or shorted. Compare sensor 

resistance values with the charted resistance in Controls Section

Water Flow (Source Heat 

Exchanger Freeze Fault)

Check status/fault lights. To check water flow remove the FS jumper (see Controls Section for location) and jumper 

the two FS terminals (located between blue and violet wires on the right side of the board) together to complete the 

flow switch circuit. Determine if the required water pressure drop is present. If required pressure drop is present, 

check the resistance of T4 source sensor (15°F=41.39kΩ; 30°F=28.61kΩ) and temperature of the refrigerant line 

between the source heat exchanger and TXV. 

High or Low 

Pressure Switches

If heat pump is out on high or low-pressure cutout (lockout), check for faulty switches by jumping the high and 

low-pressure switches individually. If defective replace. Check airflow, filters, water flow, refrigerant pressures, and 

ambient temperature. WARNING: Only allow compressor to run for a couple of seconds with the high pressure 

switch jumped.

Defective Logic Board Relay

Jump R to Y directly on lockout board. Check for 24V at Y. If no operation and no faults occur, replace lockout board.

Hot Gas Temperature>220°F

Check status/fault lights. Check hot gas/discharge line temperature with a thermocouple type thermometer. 

WARNING: Let the unit remain off for several minutes and touch the thermocouple to the discharge line to check if it 

is cooled enough to strap/tape a thermocouple to it. Check the discharge line temperature during the next operation 

cycle to compare the temperature to the lockout temperature of 220°F. Check water/air flow. If water/air flow is 

present, check the refrigerant pressures. 

Condensate Overflow (CO)

Check status/fault lights. Check sensors for contact with water, debris, or a loose sensor touching metal. Clean 

sensors if contacting debris. Flush drain lines if the drain pan is full. If no debris is present and drain pan is empty, 

remove violet wire from CO terminal on lockout board (lower right). If CO lockout occurs with violet wire removed 

replace the lockout board. 

Over/Under Voltage

Make sure secondary/low voltage is between 20V and 29V. Check the transformer’s primary connections for the 

correct voltage (Orange & Black = 230V; Red & Black = 208V). Correct any possible voltage drops in the main voltage. 

Load Heat Exchanger Frozen

Check status/fault lights. Check for reduced air flow due to dirty filter, obstructions, or poor blower performance. 

Check T1 sensor for the proper resistance (30°F = 28.61kΩ).

D: UNIT RUNNING NORMAL, BUT SPACE TEMPERATURE IS UNSTABLE

Thermostat

Thermostat is getting a draft of cold or warm air. Make sure that the wall or hole used to run thermostat wire from 

the ceiling or basement is sealed, so no draft can come to the thermostat.

Faulty Thermostat (Replace).

Section 12: Troubleshooting

Summary of Contents for WS036

Page 1: ...Installation OperationsManual WS MODELS WATER TO WATER HEAT PUMPS HYDRONIC AIR HANDLERS 20D817 21NN 20D817 21NN...

Page 2: ...nection 16 Section 6 Antifreeze Antifreeze Overview 17 Pipe Fluid Volume Table 18 Antifreeze Percentages by Volume Table 18 Antifreeze Specific Gravity Table 18 Section 7 Desuperheater Installation De...

Page 3: ...Parameters 37 Pressure Drop Tables 38 Section 12 Troubleshooting Troubleshooting Tips 39 Troubleshooting Tips 40 Compressor Troubleshooting Tips 41 Refrigeration Troubleshooting Table 42 Superheat Su...

Page 4: ...e S Single Stage Unit Capacity Nominal MBTUH 036 048 060 072 084 Revision E Current Revision Voltage 1 208 230V 60Hz 1Ph Residen al 0 208 230V 60Hz 1Ph Commercial 2 208 230V 60Hz 3Ph Commercial 3 460V...

Page 5: ...ts Use caution to not damaged the finished surface of the unit Keep all cardboard or other packaging material for safe storage and transport to the job site prior to installation Remove the front serv...

Page 6: ...TION WILL VOID ALL WARRANTIES Consumer Instructions Dealer should instruct the consumer in proper operation maintenance filter replacements thermostat and indicator lights Also provide the consumer wi...

Page 7: ...the job site Pre Installation Before you fully install the geothermal equipment it is recommended you do the following Fully inspect the unit after unpacking Locate the Unit Start Up form from this ma...

Page 8: ...ter of 120 F the loop would have to maintain 35 F to operate within the acceptable operating conditions for the compressor Once your loop temperatures drop below 35 F the acceptable leaving load tempe...

Page 9: ...Enertech Global LLC 9 WS Rev E Models Installation and Operations Manual Unit Dimensional Data Section 4 Unit Data Information...

Page 10: ...5 60 01 208 230 1 178 0 30 8 0 5 0 0 31 3 39 0 70 10 208 230 1 178 0 30 8 0 0 5 5 36 3 44 0 70 11 208 230 1 178 0 30 8 0 5 5 5 36 8 44 5 70 20 208 230 3 136 0 19 6 0 0 0 0 19 6 24 5 40 21 208 230 3 13...

Page 11: ...the internal parts are two of the potential problems The Department of Natural Resources or your local municipality can direct you to the proper testing agency See Water Quality Table for guidelines W...

Page 12: ...ng materials HDPE copper brass or rubber hose hose kit only Typical Single Compressor Unit Piping Connection The following drawings indicate typical GSHP connections Please refer to product dimensiona...

Page 13: ...ill a closed system where the fluid will not evaporate If the earth loop header is external the loop system will still need to be flushed with a purge cart The non pressurized flow center needs to be...

Page 14: ...izontal position Acceptable mounting positions for Flo Link and GPM series flow centers Equally important to pump longevity is terminal box orientation See Acceptable terminal box locations for UPS26...

Page 15: ...t lowered water flow too much and essentially taken the flow regulator out of the equation It s a good idea to remove the ball valve handles once the system is completed to avoid nuisance service call...

Page 16: ...ule Wiring Schematic provides a layout of the board The module must be mounted in a NEMA enclosure or inside the unit control box Local code supersedes any recommendations in this document DC Bridge L...

Page 17: ...e and is mid to low price The biggest down side is that it is flammable in concentrations greater than 25 Ethanol Grain alcohol which by the ATF Alcohol Tobacco Firearms department of the U S governme...

Page 18: ...eeze solutions are shown in pure form not premixed Concentrations below 25 30 consult manufacturer typically require additional inhibitors 0 9600 0 9700 0 9800 0 9900 1 0000 1 0100 1 0200 1 0300 1 040...

Page 19: ...ng from water heater 5 Thread the MPT x 3 1 2 nipple into the water heater drain port Use Teflon tape or pipe dope on threads 6 Thread the center port of the brass tee to the other end of the nipple 7...

Page 20: ...ter Tank Brass Tee Adapter to Unit Water Line Drain Copper Tee For Domestic Cold Water In Line WARNING TO AVOID SERIOUS INJURY IT IS RECOMMENDED THAT AN ANTI SCALD MIXING VALVE IS INSTALLED ON THE HOT...

Page 21: ...r actual fitting and port locations Section 7 Desuperheater Installation Air Vent Locatedat System High Point Desuperheater Out Desuperheater In Heat Pump ColdWater Supply Hot Water Water Heater orSto...

Page 22: ...ence of operation section Loop Pump Circuit Breakers The loop pump s and HWG pump are protected by control box mounted circuit breakers for easy wiring of pumps during installation Circuit breakers el...

Page 23: ...perature T2 is higher than 220 F the HWG pump will be de energized All of the issues above will break the circuit of the HWG pump via the HWG signal from the lockout board and will not lockout the com...

Page 24: ...N ON FLASH ON JUMPER FS A FRZ TEST O V NOTES 2 WHEN THE TEST JUMPER IS PULLED GREEN STATUS LED WILL BE OFF 5 NOT ALL MODELS HAVE THIS FEATURE 6 THIS FAULT INDICATES A BAD SENSOR OPEN SHORTED OR DISCON...

Page 25: ...n status light blinking Over Under Voltage Disable O U When the O U jumper is installed the over under voltage feature is active When the jumper is removed the over under voltage feature is disabled O...

Page 26: ...Enertech Global LLC 26 WS Rev E Models Installation and Operations Manual Section 10 WS Wiring Diagram WS 036 084 Wiring Diagram...

Page 27: ...ct voltage Orange Black 230V Red Black 208V Correct any possible voltage drops in the main voltage 3 Set the thermostat to Heat or Cool Adjust set point to energize the unit System will energize after...

Page 28: ...ater Pressure In Source Water Pressure Out Source Water Pressure Drop F F F F F F Heat of Rejection Extraction BTU HR BTU HR F F F F F F Cooling Heating F F F F F F Heating F F F Heating V A GA A Sour...

Page 29: ...ischarge Suction Subcooling Superheat Source Water Temp Rise Load Water Temp Drop F GPM Ton GPM Ton F PSIG PSIG F F F F 40 173 242 68 104 12 28 5 16 13 19 4 9 45 173 242 75 110 12 28 5 15 14 20 4 9 50...

Page 30: ...3 1 7 2 17 3 4 7 8 3 4 7 8 18 4 1 9 5 4 1 9 5 12 1 6 3 7 6 2 14 3 1 6 3 7 14 1 8 4 2 6 2 14 3 1 8 4 2 15 1 9 4 4 7 8 18 0 1 9 4 4 16 2 1 4 8 8 2 18 9 2 1 4 8 18 2 5 5 8 2 5 5 8 19 2 7 6 2 2 7 6 2 20...

Page 31: ...ove the FS jumper see Controls Section for location and jumper the two FS terminals located between blue and violet wires on the right side of the board together to complete the flow switch circuit De...

Page 32: ...ge the valve Always use dry nitrogen when brazing Replace filter drier any time the circuit is opened Heat pump will not cool but will heat Heat pump will not heat but will cool Reversing valve does n...

Page 33: ...s Check contactor and 24 Volt coil Check capacitor connections check capacitor with capacitor tester If ohm meter reads 0 short resistance from C to S S to R R to C or from anyone of one of these term...

Page 34: ...14 8 14 10 16 10 16 19 24 19 24 18 22 9 12 Superheat Subcooling Conditions Typical R 410A Unit Superheat Subcooling Values Refrigeration Troubleshooting Table Condition Mode Discharge Pressure Suction...

Page 35: ...__________________________________________________________ City _____________________________State Prov __________ Email ___________________________________________ Application Residential New Constru...

Page 36: ...Enertech Global LLC 36 WS Rev E Models Installation and Operations Manual This page left blank for Warranty Form detachment...

Page 37: ...Enertech Global LLC 37 WS Rev E Models Installation and Operations Manual Revision Table Date Description of Revision Page 04MAR2022 IOM and Wiring Diagram updated ALL Section 14 Revision Table...

Page 38: ...Enertech Global LLC 38 WS Rev E Models Installation and Operations Manual This page intentionally left blank...

Page 39: ...Enertech Global LLC 39 WS Rev E Models Installation and Operations Manual This page intentionally left blank...

Page 40: ...e most up to date information please visit our website or contact our Customer Service department at info enertechgeo com Statements and other information contained herein are not express warranties a...

Reviews: