Enertech WS036 Installation & Operation Manual Download Page 23

Enertech Global, LLC

23

WS Rev. E Models

Installation and Operations Manual

Temperature vs Resistance Characteristics of Sensor

Temp. (°F)

Rst. (KΩ)

Temp. (°F)

Rst. (KΩ)

10

46.95

130

3.60

15

41.39

200

1.16

20

36.50

220

0.87

30

28.61

250

0.59

77

10.00

257

0.54

Over/Under Voltage Protection

The lockout board protects the compressor from operating 

when an over/under voltage condition exists. The control 

monitors secondary voltage (24VAC) to determine an over/

under voltage condition is occurring on the primary side of 

the transformer. For example, if the secondary voltage is 

18VAC, the primary voltage for a 240V unit would be 

approximately 180V which is below the minimum voltage 

(197V) recommended by the compressor manufacturer.  

Under voltage (<18VAC) causes the compressor to disengage 

and restart when the voltage returns to >20VAC. Over voltage 

(>31VAC) causes the compressor to disengage and restart 

when the voltage returns to <29VAC.
When an O/U Voltage condition occurs, the board will initiate 

a fault, shut down the compressor, and start the five minute 

ASC period. All four fault LEDs will flash (HP + LP + FS + CO) 

and the thermostat “Call For Service” indicator will be 

illuminated. This feature is self-resetting and never retries or 

locks out. If voltage returns to normal range normal operation 

will resume if/when the ASC period is over.  When normal 

operation is restored the four fault LED’s will stop flashing 

and the “Call For Service” indicator will turn off.

Fault Retry

All faults (except O/U Voltage) are retried twice before finally 

locking the unit out. The fault retry feature is designed to 

prevent nuisance service calls. There is an anti-short cycle 

(ASC) period (5 min.) between fault retries. On the third fault 

within 30 minutes, the board will go into lockout mode and 

the “Call For Service” indicator on the thermostat will 

illuminate.

Intelligent Lockout Reset

If the thermostat is powered off for one minute then back on 

(soft reset), the board will reset and the last fault will be 

stored in memory for ease of troubleshooting. If power is 

interrupted to the board, the fault memory will be cleared.

Lockout with Emergency Heat

While in lockout mode, if the thermostat is calling for 

auxiliary heat (W1), emergency heat mode will energize. W2 

is energized two minutes after W1 is energized.

Hot Water Generator (HWG) Pump Control (If 

equipped with Desuperheater)

Controls check for HWG temperature (T3) and hot gas 

(compressor discharge) line (HGT) temperature (T2). The hot 

water generator pump is de-energized when the leaving 

water temperature (T3) is above 130°F or when the 

compressor discharge line (T2) is cooler than leaving water 

temperature (T3).  Also when the hot gas line temperature 

(T2) is higher than 220°F, the HWG pump will be de-

energized. All of the issues above will break the circuit of the 

HWG pump (via the HWG signal from the lockout board) and 

will not lockout the compressor except when T2>220°F. Units 

without a HWG also do not have sensors T2 and T3. The 

control ignores T2 and T3 and disables Faults 15 and 16, 

Sensor BAD.

Temperature Sensor Operating Range

Sensor’s Name

R

ange(°F)

T1

10 – 220

T2

20 – 257

T3

20 – 220

T4

10 – 220

Load Heat Exchanger Freeze-T1 (If equipped - units with 

coaxial heat exchangers): 

When in cooling mode, if the heat 

exchanger temperature is lower than 30°F for 30 continuous 

seconds, the compressor operation will be interrupted, and 

the control will go into fault retry mode. This sensor is located 

on the refrigerant line in between the heat exchanger and 

TXV (refrigerant inlet of heat exchanger in cooling mode).

Source Heat Exchanger Freeze -T4 (If equipped - units with 

coaxial heat exchangers): 

When in heating mode, if the heat 

exchanger is lower than setpoint for 30 continuous seconds, 

the compressor operation will be interrupted, and the control 

will go into fault retry mode. The setpoint is 12°F for closed 

loop (A-FRZ jumper removed) and 30°F (A-FRZ jumper 

installed) for open loop. At startup, the flow sensor is not 

monitored for 30 seconds to avoid nuisance faults. This 

sensor is located on the refrigerant line in between the 

source heat exchanger and TXV (refrigerant inlet of heat 

exchanger in heating mode).

Hot Gas Line Temperature limit (T2>220°F): 

When T2 is 

>220°F for 30 continuous seconds, the compressor operation 

will be interrupted. The control will go into fault retry mode.

Section 8: Controls

Over/Under Voltage Protection

The lockout board protects the compressor from operating 

when an over/under voltage condition exists. The control 

monitors secondary voltage (24VAC) to determine an over/

under voltage condition is occurring on the primary side of 

the transformer. For example, if the secondary voltage is 

18VAC, the primary voltage for a 240V unit would be 

approximately 180V which is below the minimum voltage 

(197V) recommended by the compressor manufacturer.  

Under voltage (<18VAC) causes the compressor to disengage 

and restart when the voltage returns to >20VAC. Over voltage 

(>31VAC) causes the compressor to disengage and restart 

when the voltage returns to <29VAC.
When an O/U Voltage condition occurs, the board will initiate 

a fault, shut down the compressor, and start the five minute 

ASC period. All four fault LEDs will flash (HP + LP + FS + CO) 

and the thermostat “Call For Service” indicator will be 

illuminated. This feature is self-resetting and never retries or 

locks out. If voltage returns to normal range normal operation 

will resume if/when the ASC period is over.  When normal 

operation is restored the four fault LED’s will stop flashing 

and the “Call For Service” indicator will turn off.

Summary of Contents for WS036

Page 1: ...Installation OperationsManual WS MODELS WATER TO WATER HEAT PUMPS HYDRONIC AIR HANDLERS 20D817 21NN 20D817 21NN...

Page 2: ...nection 16 Section 6 Antifreeze Antifreeze Overview 17 Pipe Fluid Volume Table 18 Antifreeze Percentages by Volume Table 18 Antifreeze Specific Gravity Table 18 Section 7 Desuperheater Installation De...

Page 3: ...Parameters 37 Pressure Drop Tables 38 Section 12 Troubleshooting Troubleshooting Tips 39 Troubleshooting Tips 40 Compressor Troubleshooting Tips 41 Refrigeration Troubleshooting Table 42 Superheat Su...

Page 4: ...e S Single Stage Unit Capacity Nominal MBTUH 036 048 060 072 084 Revision E Current Revision Voltage 1 208 230V 60Hz 1Ph Residen al 0 208 230V 60Hz 1Ph Commercial 2 208 230V 60Hz 3Ph Commercial 3 460V...

Page 5: ...ts Use caution to not damaged the finished surface of the unit Keep all cardboard or other packaging material for safe storage and transport to the job site prior to installation Remove the front serv...

Page 6: ...TION WILL VOID ALL WARRANTIES Consumer Instructions Dealer should instruct the consumer in proper operation maintenance filter replacements thermostat and indicator lights Also provide the consumer wi...

Page 7: ...the job site Pre Installation Before you fully install the geothermal equipment it is recommended you do the following Fully inspect the unit after unpacking Locate the Unit Start Up form from this ma...

Page 8: ...ter of 120 F the loop would have to maintain 35 F to operate within the acceptable operating conditions for the compressor Once your loop temperatures drop below 35 F the acceptable leaving load tempe...

Page 9: ...Enertech Global LLC 9 WS Rev E Models Installation and Operations Manual Unit Dimensional Data Section 4 Unit Data Information...

Page 10: ...5 60 01 208 230 1 178 0 30 8 0 5 0 0 31 3 39 0 70 10 208 230 1 178 0 30 8 0 0 5 5 36 3 44 0 70 11 208 230 1 178 0 30 8 0 5 5 5 36 8 44 5 70 20 208 230 3 136 0 19 6 0 0 0 0 19 6 24 5 40 21 208 230 3 13...

Page 11: ...the internal parts are two of the potential problems The Department of Natural Resources or your local municipality can direct you to the proper testing agency See Water Quality Table for guidelines W...

Page 12: ...ng materials HDPE copper brass or rubber hose hose kit only Typical Single Compressor Unit Piping Connection The following drawings indicate typical GSHP connections Please refer to product dimensiona...

Page 13: ...ill a closed system where the fluid will not evaporate If the earth loop header is external the loop system will still need to be flushed with a purge cart The non pressurized flow center needs to be...

Page 14: ...izontal position Acceptable mounting positions for Flo Link and GPM series flow centers Equally important to pump longevity is terminal box orientation See Acceptable terminal box locations for UPS26...

Page 15: ...t lowered water flow too much and essentially taken the flow regulator out of the equation It s a good idea to remove the ball valve handles once the system is completed to avoid nuisance service call...

Page 16: ...ule Wiring Schematic provides a layout of the board The module must be mounted in a NEMA enclosure or inside the unit control box Local code supersedes any recommendations in this document DC Bridge L...

Page 17: ...e and is mid to low price The biggest down side is that it is flammable in concentrations greater than 25 Ethanol Grain alcohol which by the ATF Alcohol Tobacco Firearms department of the U S governme...

Page 18: ...eeze solutions are shown in pure form not premixed Concentrations below 25 30 consult manufacturer typically require additional inhibitors 0 9600 0 9700 0 9800 0 9900 1 0000 1 0100 1 0200 1 0300 1 040...

Page 19: ...ng from water heater 5 Thread the MPT x 3 1 2 nipple into the water heater drain port Use Teflon tape or pipe dope on threads 6 Thread the center port of the brass tee to the other end of the nipple 7...

Page 20: ...ter Tank Brass Tee Adapter to Unit Water Line Drain Copper Tee For Domestic Cold Water In Line WARNING TO AVOID SERIOUS INJURY IT IS RECOMMENDED THAT AN ANTI SCALD MIXING VALVE IS INSTALLED ON THE HOT...

Page 21: ...r actual fitting and port locations Section 7 Desuperheater Installation Air Vent Locatedat System High Point Desuperheater Out Desuperheater In Heat Pump ColdWater Supply Hot Water Water Heater orSto...

Page 22: ...ence of operation section Loop Pump Circuit Breakers The loop pump s and HWG pump are protected by control box mounted circuit breakers for easy wiring of pumps during installation Circuit breakers el...

Page 23: ...perature T2 is higher than 220 F the HWG pump will be de energized All of the issues above will break the circuit of the HWG pump via the HWG signal from the lockout board and will not lockout the com...

Page 24: ...N ON FLASH ON JUMPER FS A FRZ TEST O V NOTES 2 WHEN THE TEST JUMPER IS PULLED GREEN STATUS LED WILL BE OFF 5 NOT ALL MODELS HAVE THIS FEATURE 6 THIS FAULT INDICATES A BAD SENSOR OPEN SHORTED OR DISCON...

Page 25: ...n status light blinking Over Under Voltage Disable O U When the O U jumper is installed the over under voltage feature is active When the jumper is removed the over under voltage feature is disabled O...

Page 26: ...Enertech Global LLC 26 WS Rev E Models Installation and Operations Manual Section 10 WS Wiring Diagram WS 036 084 Wiring Diagram...

Page 27: ...ct voltage Orange Black 230V Red Black 208V Correct any possible voltage drops in the main voltage 3 Set the thermostat to Heat or Cool Adjust set point to energize the unit System will energize after...

Page 28: ...ater Pressure In Source Water Pressure Out Source Water Pressure Drop F F F F F F Heat of Rejection Extraction BTU HR BTU HR F F F F F F Cooling Heating F F F F F F Heating F F F Heating V A GA A Sour...

Page 29: ...ischarge Suction Subcooling Superheat Source Water Temp Rise Load Water Temp Drop F GPM Ton GPM Ton F PSIG PSIG F F F F 40 173 242 68 104 12 28 5 16 13 19 4 9 45 173 242 75 110 12 28 5 15 14 20 4 9 50...

Page 30: ...3 1 7 2 17 3 4 7 8 3 4 7 8 18 4 1 9 5 4 1 9 5 12 1 6 3 7 6 2 14 3 1 6 3 7 14 1 8 4 2 6 2 14 3 1 8 4 2 15 1 9 4 4 7 8 18 0 1 9 4 4 16 2 1 4 8 8 2 18 9 2 1 4 8 18 2 5 5 8 2 5 5 8 19 2 7 6 2 2 7 6 2 20...

Page 31: ...ove the FS jumper see Controls Section for location and jumper the two FS terminals located between blue and violet wires on the right side of the board together to complete the flow switch circuit De...

Page 32: ...ge the valve Always use dry nitrogen when brazing Replace filter drier any time the circuit is opened Heat pump will not cool but will heat Heat pump will not heat but will cool Reversing valve does n...

Page 33: ...s Check contactor and 24 Volt coil Check capacitor connections check capacitor with capacitor tester If ohm meter reads 0 short resistance from C to S S to R R to C or from anyone of one of these term...

Page 34: ...14 8 14 10 16 10 16 19 24 19 24 18 22 9 12 Superheat Subcooling Conditions Typical R 410A Unit Superheat Subcooling Values Refrigeration Troubleshooting Table Condition Mode Discharge Pressure Suction...

Page 35: ...__________________________________________________________ City _____________________________State Prov __________ Email ___________________________________________ Application Residential New Constru...

Page 36: ...Enertech Global LLC 36 WS Rev E Models Installation and Operations Manual This page left blank for Warranty Form detachment...

Page 37: ...Enertech Global LLC 37 WS Rev E Models Installation and Operations Manual Revision Table Date Description of Revision Page 04MAR2022 IOM and Wiring Diagram updated ALL Section 14 Revision Table...

Page 38: ...Enertech Global LLC 38 WS Rev E Models Installation and Operations Manual This page intentionally left blank...

Page 39: ...Enertech Global LLC 39 WS Rev E Models Installation and Operations Manual This page intentionally left blank...

Page 40: ...e most up to date information please visit our website or contact our Customer Service department at info enertechgeo com Statements and other information contained herein are not express warranties a...

Reviews: