Enertech Global, LLC
24
WS Rev. E Models
Installation and Operations Manual
Section 8: Controls
LED Identification
CONDITION
GREEN
HP
ORANGE
LP
RED
FS
YELLOW
CO
STATUS
GREEN L
TERMINAL
1
NORMAL
MODE
FLASH
TEST
MODE
2
HP
FAULT
FLASH
FLASH
HP
LOCKOUT
ON
FLASH
ON
LP
FAULT
FLASH
FLASH
LP
LOCKOUT
ON
FLASH
ON
SOURCE
COIL
FRZ/
WF
FAULT
(T4/FS)
3
FLASH
FLASH
SOURCE
COIL
FRZ/
WF
LOCKOUT
(T4/FS)
3
ON
FLASH
ON
LOAD/
AIR
COIL
FRZ
FAULT
(T1)
4,5
FLASH
FLASH
FLASH
LOAD/
AIR
COIL
FRZ
LOCKOUT
(T1)
4,5
ON
ON
FLASH
ON
CO
FAULT
5
FLASH
FLASH
CO
LOCKOUT
5
ON
FLASH
ON
O/
U
VOLTAGE
FLASH
FLASH
FLASH
FLASH
FLASH
ON
T1
FAULTY
5,6
FLASH
ON
FLASH
FLASH
T2
FAULTY
5,6
FLASH
ON
FLASH
FLASH
T3
FAULTY
5,6
FLASH
ON
FLASH
FLASH
T4
FAULTY
5,6
ON
FLASH
FLASH
FLASH
T1
&
T4
SWAPPED
7
ON
ON
FLASH
HOT
GAS
LINE
FAULT
>
220
F
(T2)
8
FLASH
FLASH
ON
FLASH
HOT
GAS
LINE
LOCKOUT
>
220
F
(T2)
8
ON
ON
ON
FLASH
ON
JUMPER
FS
A
‐
FRZ
TEST
O/
V
NOTES:
2.
WHEN
THE
TEST
JUMPER
IS
PULLED,
GREEN
STATUS
LED
WILL
BE
OFF.
5.
NOT
ALL
MODELS
HAVE
THIS
FEATURE.
6.
THIS
FAULT
INDICATES
A
BAD
SENSOR
(OPEN,
SHORTED,
OR
DISCONNECTED).
7.
THIS
CAN
ONLY
BE
CHECKED
WHILE
IN
TEST
MODE.
8.
HOT
GAS
LINE
IS
TOO
HOT.
OPEN
LOOP
MODE
‐
30
F
SETTING
FOR
T4
CLOSED
LOOP
MODE
‐
15
F
SETTING
FOR
T4
LOCKOUT
BOARD
LED
IDENTIFICATION
&
L
TERMINAL
STATUS
LOCKOUT
BOARD
JUMPERS
INSTALLED
REMOVED
T1
&
T4
MONITORED
FOR
FLOW
‐
'FS'
TERMINALS
IGNORED
FS'
TERMINALS
USED
FOR
FLOW
SWITCH
‐
T1
&
T4
IGNORED
REV
A.
03/25/16
4.
THE
LOAD/
AIR
COIL
FREEZE
PROTECTION
SENSOR
IS
LOCATED
BETWEEN
THE
TXV
AND
LOAD/
AIR
COIL.
OPERATES
IN
NORMAL
MODE
WITH
STANDARD
DELAYS
OPERATES
IN
TEST
MODE
WITH
DELAYS
SPED
UP
FEATURE
IS
ACTIVE
FEATURE
IS
INACTIVE
1.
THE
'L'
TERMINAL
CONTROLS
A
FAULT
LED
AT
THE
THERMOSTAT
OR
DRIVES
AN
AUXILIARY
FAULT
RELAY.
3.
DEPENDING
UPON
MODEL,
THE
SOURCE
COIL
FRZ/
WATER
FLOW
FAULT
OR
LOCKOUT
CAN
BE
AN
INTERNAL
OR
EXTERNAL
FLOW
SWITCH
(FS),
OR
A
SENSOR
(T4)
LOCATED
BETWEEEN
THE
TXV
AND
SOURCE
COIL.