ASSEMBLY AND USER MANUAL
Combi [6 | 12 | 16] & Combi 12 HT
www.energie.pt
27
7.
ERROR MESSAGES
Before seeking Technical assistance, follow the steps of this table to check whether it is needed.
ERROR (Code)
Description
Cause/Solution
Er01
–
FLOW
(During the
check up is not
not an error)
Flowmeter doesn’t work.
✓
Lack of flow on the circuit. Water circulator
disconnected or filter obstructed. Check electrical
connections of the circulator or clean filter.
✓
Poorly drained circuit. Excess air at the hydraulic
installation.
✓
Water flow too low. Increase water circulation pump
speed or replace for a larger one.
✓
Hydraulic circuit is empty (no water).
Er02
–
TN
Safety Thermostat
✓
Thermal relay action resulting from exaggerated
electrical consumption of the compressor or mains
voltage anomalies.
Er03
–
LP
Low Pressure, system
doesn’t work or
disconnects cyclically
✓
Lack of fluid or leak on circuit. Check the circuit
pressure with gauge.
✓
Low outsider temperature.
✓
Obstruction of refrigerant circuit (e.g. Humidity).
✓
Low pressure switch damaged.
Er04
–
HP
High pressure, system
doesn’t work
✓
Fluid overcharge. Check circuit pressure with
manometers.
✓
High pressure switch damaged.
✓
Poor heat exchange. Increase flow.
Er05
–
TS1
Temperature alarm
✓
Excess of temperature. Lack of water in the circuit,
circulator pump disconnected or stuck or damaged
Flowmeter.
Er05
–
TS2
Er06
–
TS3
Er07
–
TS4
Er08
–
RTC
Clock
✓
Internal clock of the controller is damaged. Replace
the controller.
✓
The controller battery is discharged or weak. Replace
the battery (type of battery CR2032)
TL
Probe Failure (S1, S2, S3
or S4)
✓
Check whether the probe is measuring correctly,
verifying its internal resistance.
✓
Verify connections.
Er11 - EVD
Alarm Relay Open on
Carel EVD
✓
Check the power supply on the EVD (fuse-Fs).
✓
Pressure/Temperature sensor connected wrongly or
damaged. Check connections or replace sensor (POS)
✓
Low Superheating (LowSH).
✓
Very low evaporation temperature (LOP).
✓
Very high evaporation temperature (MOP).
✓
Low aspiration temperature.
✓
Low aspiration pressure.
The intervention at the Combi Block must only be carried out by authorised and specialised
professionals.