Calibration with partially
filled vessel
If the following calibration during the hydrostatic level measurement is carried out with
water (density = 1g/cm3), the correction factor indicated in the V8H7 corresponds in
each case to the density of the product.
Sensor calibration
Step
Matrix
Entry
Significance
1
V9H5
e.g. 672
Reset transmitter
2
-
»E«
Register entry
Note! See also Section 4.1 Commissioning, V3H5; V3H6
3
V8H0
5
Enter operating mode
4
-
»E«
Register entry
5
V8H2
4 s
Set switching delay to min. 4 s
6
-
»E«
Register entry
7
V8H3
e.g. 80%
Enter installation height of limit switch
in desired unit
8
-
»E«
Register entry
9
V8H4
0
Enter sensor type: 0 = Liquiphant; 1 = capacitance probe
10
-
»E«
Register entry
11
V8H5
0
only for capacitance probes (channel 2)
Perform calibration with exposed probe
12
-
»E«
Register entry
13
V8H6
e.g. 1
only for capacitance probes (channel 2)
Set switching point in Hz,
Section 8.2
14
-
»E«
Register entry
Level calibration
Step
Matrix
Entry
Significance
1
V8H7
1
With vessel partially filled (0
…
40 %), enter density
(correction factor)
2
-
»E«
Register entry
3
V0H1
e.g. 10%
Enter »empty« level
4
-
»E«
Register entry
2
V8H7
1
Fill vessel (60
…
100%) and re-enter density
(correction factor)
3
-
»E«
Register entry
3
V0H2
e.g. 90%
Enter »full« level
4
-
»E«
Register entry
Note!
•
The best accuracy is attained when the difference between »full« and »empty«
levels is as great as possible.
•
If operating mode 5 is temporarily quit, the Silometer measures by using the
sensitivity V3H2 x V8H7. The indication remains correct as long as the same product
is in the tank.
•
Analogue output and relays are set as described in Chapter 6 and 7.