No.
V2H2
Volume
V2H3
Level
V2H4
No.
V2H2
Volume
V2H3
Level
V2H4
1
16
2
17
3
18
4
19
5
20
6
21
7
22
8
23
9
24
10
25
11
26
12
27
13
28
14
29
15
30
Step
Matrix
Entry
Significance
1
V9H5
e.g. 670
Reset transmitter, see Section 4.1 (default = operating mode 1)
-
Enter probe constants at V3H5 and V3H6
2
V0H1/V0H2
-
Calibrate as described in Section 4.2
3
V2H1
0
Select manual entry of values
4
-
»E«
Register entry
5
V2H2
1
…
30
Enter table entry number
6
-
»E«
Register entry
7
V2H3
e.g. 0
Enter volume in required units
8
-
»E«
Register entry
9
V2H4
00.00
Enter level for support point number
10
-
»E«
Register entry
11
V2H5
2
…
30
Second support point number will be displayed
12
-
»E«
Confirm input, the system jumps to V2H3,
the support point number is addet automatically
13
V2H3
Repeat steps 7 to 12 until the filling volume and level
have been entered for all support points
14
V2H0
3
Select manual linearization table
15
-
»E«
Press »E« to activate linearization
16
V0H0/V0H9
-
Display of volume and level before linearisation
Note!
•
Set analogue output and relay switch point in same units as used for linearization
Manual linearization
with tabular values
Silometer FMC 671 Z/676 Z
Chapter 5: Linearization
30