2.5
Hardware configuration
Fig. 2.10 shows the configuration elements for remote operation of the Silometer
FMC 671 Z/676 Z transmitter.
Commulog VU 260 Z
The Silometer is supplied configured for operation with the Commulog handheld terminal,
with the hook switch connected to the contact nearest the front panel.
•
If the handheld terminal is to be used during computer operation, the card
must first be reconfigured for Commulog operation
Gateway ZA 67...
Configure the Silometer card for remote operation via the ZA 672 Modbus gateway
(or ZA 67
…
computer interface) as follows:
•
Set the hook switch to ZA 672/ZA 67
…
operation as indicated (contact
nearest the backplane connector).
•
Set a unique device address between 0 and 63 at the address switch.
-
When off, each switch has the value 0.
-
When on, each switch is assigned the value shown in Fig. 2.10, inset.
In the example the address is 2 + 8 = 10.
A full description of ZA 672 operation is to be found in Publication BA 054F/00/en.
Caution!
•
Electrostatic discharge can degrade performance or damage electronic modules.
Touch a grounded object to rid yourself of charge before handling the modules.
Front panel
BA063E20/21
Communication via sockets at
front side: VU 260 Z (Default)
Female
multipoint
connector
Address = 2 + 8 = 10
Communication via female multipoint
connector contacts: ZA 67...
Address
switch
Communications
switch
Fig. 2.10:
Configuration elements of
Silometer FMC 671 Z/676 Z
shown for Commulog operation
Silometer FMC 671 Z/676 Z
Chapter 2: Installation
17