Sensor calibration
with vessel empty
Step
Matrix
Entry
Significance
1
V9H5
e.g. 672
Reset transmitter
2
-
»E«
Register entry
Note! See also Section 4.1 Commissioning, V3H5; V3H6
3
V8H0
5
Enter operating mode
4
-
»E«
Register entry
5
V8H2
4 s
Set switching delay to min. 4 s
6
-
»E«
Register entry
7
V8H3
e.g. 80%
Enter installation height of limit switch in same unit
as level in channel 1
8
-
»E«
Register entry
9
V8H4
0
Enter sensor type: 0 = Liquiphant; 1 =capacitance probe
10
-
»E«
Register entry
11
V8H5
0
only for capacitance probes (channel 2)
Perform calibration with exposed probe
12
-
»E«
Register
entry
13
V8H6
e.g. 1
only for capacitance probes (channel 2)
Set switching point in Hz,
Section 8.2
14
-
»E«
Register
entry
16
V8H7
1
Set correction factor to 1.0
17
-
»E«
Register entry
"Empty" calibration
Step
Matrix
Entry
Significance
1
V0H1
0%
Enter »empty«level of zero
2
-
»E«
Register entry
Note!
•
The »full« calibration is carried out automatically when the product reaches the
switching probe. Since the default display sensitivity is used during this time, the display
at V0H0 may be initially incorrect and analogue signal/relays not function as set.
•
Analogue output and relays are set as described in Chapter 6 and 7.
BA063D28
Level check
capacitance
probe or
liquiphant
Level measurement
with Deltapilot
Channel 1
Level measurement with
capacitance probe
Level
Channel 2
Relays 1
and 2
Level
or
Fig. 8.7:
Arrangement for
continuous level measurement
with automatic calibration
correction
Silometer FMC 671 Z/676 Z
Chapter 8: Other Applications
48