8.3
Continuous level measurement with separate
level limit detection
Operating mode 0 allows level measurement on channel 1 and level switching on
channel 2.
If a Deltapilot S is being used, only a Liquiphant can be used as limit switch.
Each channel is assignet to a relay.
•
Relay 1 (channel 1) and relay 2 (channel 2) are set as described in Chapter 6
and Section 8.2.
•
Calibration for each channel is as described in Chapter 4 and Section 8.2.
For capacitance probes the system can be calibrated as follows:
Level limit probe
calibration with
empty vessel
Step
Matrix
Entry
Significance
1
V9H5
e.g. 672
Reset transmitter
2
-
»E«
Register entry
3
V8H0
0
Select level switching mode
4
-
»E«
Register entry
5
V8H4
1
Set sensor type to capacitance probe
6
-
»E«
Register entry
7
V8H6
e.g. 1
Set switching point in Hz
8
-
»E«
Register entry
9
V8H5
0
Calibrate with probe uncovered
10
-
»E«
Register entry (must be pressed!!)
Level calibration
Step
Matrix
Entry
Significance
1
V0H1
e.g. 10%
With vessel 0
…
40% full, enter current level
2
-
»E«
Register entry
3
V0H2
e.g. 90%
With vessel 60
…
100% full, enter current level
4
-
»E«
Register entry
Probe 1
continuous
measurement
Probe 2
limit switching
Level
Channel 1
Relay 1 = level
Relay 2 = switching
Channel 2
BA063D45
Fig. 8.5:
Operating mode 0
Continuous level measurement
with simultaneous level switching
Silometer FMC 671 Z/676 Z
Chapter 8: Other Applications
46