Commissioning
RIA452
132
Hauser
6.3.8
Min/Max memory - MIN MAX/M20
The process display unit can save a minimum and a maximum measured value. The input signal
or the signal processed using the linearization table are available as the signal source. The
memory is reset manually or using the digital input (see Section 6.3.4).
Function
(menu
item)
Parameter setting
Description
Dec. value
XXXXX
XXXX.X
XXX.XX
XX.XXX
X.XXXX
Decimal point position of the pulse value.
Unit value
0..99999
1.0
Pulse value with which the pulses should be output at
the output.
Pulse width
0.04 to 2000ms
1000.00
Sets the pulse width at the pulse output.
!
Note!
The maximum output frequency depends on the pulse
width.
f(max) = 1/(2*pulse width)
Sim pulseout
Off
1 Hz
10 Hz
100 Hz
1000 Hz
10000 Hz
Outputs the selected pulses at the pulse output
regardless of the input value.
Is automatically set to OFF when exited.
Function
(menu
item)
Parameter setting
Description
Ref. min/max
Input
Lintab
Signal source for the min/max value memory.
• Input = input signal
• Lintab = linearized input signal or current flow value
for channel calculation