RIA452
Commissioning
Hauser
105
6
Commissioning
6.1
Function check
Make sure that all post-connection checks have been carried out before you commission your
device:
• Checklist Section 4.3 'Post-connection check'
!
Note!
Remove the protective strip from the display as this restricts display legibility otherwise.
6.2
Switching on the measuring device
Once the operating voltage is applied, the green LED indicates that the instrument is operational.
• When the unit is delivered, the device parameters are used as per the factory settings.
• When commissioning a device already configured or preset, measuring is immediately started
as per the settings. The limit values only switch once the first measured value has been
determined.
• The limit values are only activated as per their configuration once a valid measured value is
present.
6.3
Device configuration
This section describes all the configurable instrument parameters with the associated value
ranges and factory settings (default values, marked in bold).
6.3.1
Analog input - INPUT/M1
All the parameters that can be selected for the input can be found under the analog input menu
item which is marked as INPUT in the device.