Proline Promag 55 PROFIBUS PA
Wiring
Hauser
47
4.4
Connecting the measuring unit
4.4.1
Connecting the transmitter
#
Warning!
• Risk of electric shock. Switch off the power supply before opening the device. Do not install or
wire the device while it is connected to the power supply. Failure to comply with this precaution
can result in irreparable damage to the electronics.
• Risk of electric shock. Connect the protective earth to the ground terminal on the housing before
the power supply is applied (e.g. galvanically isolated power supply SELV or PELV).
• Compare the specifications on the nameplate with the local voltage supply and frequency. Also
observe the national regulations governing the installation of electrical equipment.
Procedure (Fig. 33):
1.
Unscrew the connection compartment cover (a) from the transmitter housing.
2.
Feed the power supply cable (b) and fieldbus cable (d) through the appropriate cable entries.
3.
Perform wiring in accordance with the respective terminal assignment and the associated
wiring diagram.
"
Caution!
– Risk of damage to the fieldbus cable!
Observe the information about shielding and grounding the fieldbus cable
– We recommend that the fieldbus cable not be looped using conventional cable glands. If you
later replace even just one measuring device, the bus communication will have to be
interrupted.
4.
Screw the cover of the connection compartment (a) back onto the transmitter housing.