PROline Promag 10
11 Description of Device Functions
Hauser
113
ALARM DELAY
Use this function to define a time span in which the criteria for an error have to
be satisfied without interruption before an error or notice message is
generated.
Depending on the setting and the type of error, this suppression acts on:
• Display
• Current output
• Pulse/status output
User input:
0...100 s (in steps of one second)
Factory setting:
0 s
"
Caution!
If this function is activated error and notice messages are delayed by the time
corresponding to the setting before being forwarded to the higher-order
controller (process controller, etc.). It is therefore imperative to check in
advance in order to make sure whether a delay of this nature could affect the
safety requirements of the process.
If error and notice messages cannot be suppressed, a value of 0 seconds
must be entered here.
SYSTEM RESET
Use this function to perform a reset of the measuring system.
Options:
NO
RESTART SYSTEM
(Restart without disconnecting main power)
RESET DELIVERY
(Restart without disconnecting main power, the saved settings of the delivery
status (factory settings) are applied).
Factory setting:
NO
Function description SUPERVISION