Installation height as per
IEC61010-1 Ed.3
• Generally up to 2
000 m (6
600 ft) above sea level
• Over 2
000 m (6
600 ft) under the following conditions:
• Supply voltage < 35 V
DC
• Power supply, overvoltage category 1
Degree of protection
Test as per IEC 60529 and NEMA 250-2014
Housing and process connection
IP66/68, TYPE 4X/6P
(IP68: (1.83 mH
2
O for 24 h))
Cable entries
• Gland M20, plastic, IP66/68 TYPE 4X/6P
• Gland M20, brass nickel plated, IP66/68 TYPE 4X/6P
• Gland M20, 316L, IP66/68 TYPE 4X/6P
• Thread M20, IP66/68 TYPE 4X/6P
• Thread G1/2, IP66/68 TYPE 4X/6P
If the G1/2 thread is selected, the device is delivered with an M20 thread as standard
and a G1/2 adapter is included with the delivery, along with the corresponding
documentation
• Thread NPT1/2, IP66/68 TYPE 4X/6P
• HAN7D plug, 90 degrees, IP65 NEMA Type 4X
• M12 plug
• When housing is closed and connecting cable is plugged in: IP66/67 NEMA Type 4X
• When housing is open or connecting cable is not plugged in: IP20, NEMA Type 1
NOTICE
Plug M12 and plug HAN7D: incorrect mounting can invalidate the IP protection class!
‣
The degree of protection only applies if the connecting cable used is plugged in and
screwed tight.
‣
The degree of protection only applies if the connecting cable used is specified according
to IP67 NEMA Type 4X.
‣
The IP protection classes are only maintained if the dummy cap is used or the cable is
connected.
Vibration resistance
DIN EN 60068-2-64 / IEC 60068-2-64 for 5 to 2
000 Hz: 1.5 (m/s
2
)
2
/Hz
Electromagnetic
compatibility (EMC)
• Electromagnetic compatibility as per EN 61326 series and NAMUR recommendation
EMC (NE21)
• With regard to the safety function (SIL), the requirements of EN 61326-3-x are satisfied
• Maximum measured error during EMC testing: < 0.5 % of the span.
For more details refer to the EU Declaration of Conformity.