Technical data
Micropilot FMR67B HART
64
Hauser
The current output offers a choice of three different operating modes:
• 4.0 to 20.5 mA
• NAMUR NE 43: 3.8 to 20.5 mA (factory setting)
• US mode: 3.9 to 20.8 mA
Signal on alarm
Current output
Failure mode (according to NAMUR Recommendation NE 43):
• Minimum alarm (= factory setting): 3.6 mA
• Maximum alarm: 22 mA
Local display
Status signal (according to NAMUR Recommendation NE 107):
Plain text display
Operating tool via service interface (CDI)
Status signal (according to NAMUR Recommendation NE 107):
Plain text display
Operating tool via HART communication
Status signal (according to NAMUR Recommendation NE 107):
Plain text display
Linearization
The linearization function of the device allows the conversion of the measured value into
any unit of length, weight, flow or volume.
Pre-programmed linearization curves
Linearization tables for calculating the volume in the following vessels are preprogrammed
into the device:
• Pyramid bottom
• Conical bottom
• Angled bottom
• Horizontal cylinder
• Sphere
Other linearization tables of up to 32 value pairs can be entered manually.