Operating menu
Micropilot FMR20 HART
98
Hauser
15.4.2 "Simulation" submenu
Navigation
Diagnostics → Simulation
Simulation
Navigation
Diagnostics → Simulation → Simulation
Description
Select process variable to be simulated.
The Simulation is used to simulate specific measuring values or other conditions. This
helps to check the correct configuration of the device and connected control units.
Selection
• Off
• Current output
• Distance
Value current output
Navigation
Diagnostics → Simulation → Value curr.out 1
Description
Defines the value of the simulated output current.
User entry
3.59 to 22.5 mA
Process variable value
Navigation
Diagnostics → Simulation → Proc. var. value
Description
Value of the simulated process variable.
Downstream measured value processing and the signal output use this simulation value. In
this way, users can verify whether the measuring device has been configured correctly.
User entry
0 to 21.8 m