Micropilot FMR20 HART
Commissioning and operation
Hauser
35
Using the following operating matrix, a display in percent can be set. To do this, select
"Mode" parameter => 4-20 and "Unit" parameter =>%
MENU SETUP
Parameters
Values
visible at
Description
MODE
4-20
HART
Select the operating mode for the
indicator
4-20: The circuit's 4 to 20 mA signal is
displayed
HART: Up to four HART variables (PV,
SV, TV, QV) per sensor/actuator can be
displayed in the loop.
DECIM
0 DEC
1 DEC
2 DEC
3 DEC
4 DEC
MODE = 4-20
Number of decimal places for display
SC__4
Numerical value
–19
999 to 99
999
Default:
0.0
MODE = 4-20
5-digit value (number of decimal places
as configured under DECIM) for scaling
the measured value
at 4 mA Example: SC__4 = 0.0 => 0.0
displayed for measuring current of
4 mA
The unit selected under UNIT is used to
display the value.
SC_20
Numerical value
–19
999 to 99
999
Default:
100.0
MODE = 4-20
5-digit value (number of decimal places
as configured under DECIM) for scaling
the measured value
at 20 mA Example: SC__20 = 100.0 =>
100.0 displayed for measuring current
of 20 mA
The unit selected under UNIT is used to
display the value.
UNIT
%
°C
°F
K
USER
MODE = 4-20
Use this function to select the unit for
displaying the value. If "USER" is
selected, a user-defined unit can be
entered in the TEXT parameter.
TEXT
Customized text, 5-digit
MODE = 4-20
User-defined unit, only visible if the
"USER" option has been selected under
UNIT.
Any additional settings such as linearizations must be made using FieldCare,
DeviceCare or SmartBlue
Additional information is available in the RIA15 Operating Instructions BA01170K