![Endress+Hauser Liquisys M CLM223/253 Operating Instructions Manual Download Page 12](http://html1.mh-extra.com/html/endress-hauser/liquisys-m-clm223-253/liquisys-m-clm223-253_operating-instructions-manual_2408535012.webp)
Mounting
Liquisys M CLM223/253
12
Hauser
3.3
Installation instructions
3.3.1
Field instrument
There are several ways of securing the field housing:
• Wall mounting with fixing screws
• Post mounting to cylindrical pipes
• Post mounting to square securing masts
NOTICE
Effect of climate conditions (rain, snow, direct sun etc.)
Impaired operation to complete transmitter failure
‣
When installing outside, always use the weather protection cover (accessory).
Transmitter wall mounting
a0005736
Fig. 5:
Wall mounting field device
For wall mounting the transmitter, proceed as follows:
1. Drill the bores as shown in
å
5.
2. Drive the two fixing screws through the securing bores (1) from the front.
3. Mount the transmitter on the wall as shown.
4. Cover the bores with plastic caps (2).
1
2
154 / 6.06
mm / inch
Ø6/ Ø
0.24
Summary of Contents for Liquisys M CLM223/253
Page 112: ...www addresses endress com 71212629...