Levelflex M FMP40 with HART/4...20 mA
Operation
Hauser
41
5.4
Displaying and acknowledging error messages
Type of error
Errors that occur during commissioning or measuring are displayed immediately on the local
display. If two or more system or process errors occur, the error with the highest priority is the one
shown on the display.
The measuring system distinguishes between the following types of error:
•
A (Alarm):
Device goes into a defined state (e.g. MAX 22 mA)
Indicated by a constant symbol .
(For a description of the codes see
•
W (Warning):
Device continues measuring, error message is displayed.
Indicated by a flashing
symbol.
(For a description of the codes see
•
E (Alarm / Warning):
Configurable (e.g. loss of echo, level within the safety distance)
Indicated by a constant/flashing symbol
.
(For a description of the codes see
Error messages
Error messages appear as four lines of plain text on the display. In addition, a unique error code is
also output. A description of the error codes is given on
• The "
Diagnostics
"
(0A)
function group can display the current error as well as the last error that
occurred.
• If several errors are pending, use
O
or
S
to scroll through the error messages.
• The last error to occur can be deleted in the "
Diagnostics
"
(0A)
function group "
Clear Last.
Error
"
(0A2)
function.
⇒
E HAUSER
E
+
–
Summary of Contents for Levelflex M FMP40
Page 4: ...Brief overview Levelflex M FMP40 with HART 4 20 mA 4 Endress Hauser...
Page 87: ...Levelflex M FMP40 with HART 4 20 mA Appendix Endress Hauser 87...
Page 88: ...Appendix Levelflex M FMP40 with HART 4 20 mA 88 Endress Hauser...
Page 90: ...Levelflex M FMP40 with HART 4 20 mA Index 90 Endress Hauser...
Page 92: ...www endress com worldwide BA363F 00 en 03 09 No 71074941 CCS FM SGML 6 0 ProMoDo 71074941...