Levelflex M FMP40 with HART/4...20 mA
Commissioning
Hauser
49
Function "Process Propert." (004)
Use this function to adapt the device reaction to the filling speed in the tank. The setting influences
an intelligent filter and affects the total level and interface layer level in the same way.
Options:
•
Standard
• Fast change
• Slow change
• Test: no Filter
Function "Empty Calibr." (005)
This function is used to enter the distance from the flange (reference point of the measurement) to
the minimum level (=zero).
L00-FMP4xIxx-14-00-06-en-001
⇒
E HAUSER
E
+
–
Options:
Standard
Fast Change
Slow Change
Test: No Filter
Application:
For all normal applications with
low to medium filling speeds and
sufficiently large tanks.
Small tanks, primarily with
liquids, at high filling speeds.
Applications with slow to
medium filling speeds.
Shortest reaction time:
• For test purposes
• Measurement in small tanks
at high filling speeds, if "Fast
Change" setting is too slow.
2-wire electronics:
Dead time: 4 s
Rise time: 18 s
Dead time: 2 s
Rise time: 5 s
Dead time: 6 s
Rise time: 40 s
Dead time: 1 s
Rise time: 0 s
⇒
E HAUSER
E
+
–
0%
E
E = empty calibration (= zero)
Summary of Contents for Levelflex M FMP40
Page 4: ...Brief overview Levelflex M FMP40 with HART 4 20 mA 4 Endress Hauser...
Page 87: ...Levelflex M FMP40 with HART 4 20 mA Appendix Endress Hauser 87...
Page 88: ...Appendix Levelflex M FMP40 with HART 4 20 mA 88 Endress Hauser...
Page 90: ...Levelflex M FMP40 with HART 4 20 mA Index 90 Endress Hauser...
Page 92: ...www endress com worldwide BA363F 00 en 03 09 No 71074941 CCS FM SGML 6 0 ProMoDo 71074941...