Levelflex M FMP 40 with Foundation Fieldbus
6 Commissioning
Hauser
67
Display (008)
The distance measured from the reference point to the product surface and the meas.
value calculated with the aid of the empty alignment are displayed again. Check
whether the values correspond to the actual meas. value or the actual distance. The
following cases can occur:
•
Distance correct – meas. value correct -> basic setup completed
•
Distance incorrect – meas. value incorrect -> a further interference echo mapping
must be carried out "
check distance
" (
051)
.
•
Distance correct – meas. value incorrect -> check "
empty calibr.
"
(005)
!
Note!
After the basic setup, an evaluation of the measurement with the aid of the envelope
curve ("
envelope curve
"
(0E)
" function group) is recommended (see page 99).
6.5
Blocking distnace
!
Note!
At installation in high nozzles, please the blocking distance in the function
"
upper block.dist
"
(059)
newly enter!
⇒
⇒
⇓