4 Wiring
Levelflex M FMP 40 with Foundation Fieldbus
30
EHauser
Wiring with M12 connector
4.2
Cable specifications Foundation Fieldbus
Twisted, shielded pairs must be used. The cable specifications can be taken from the
FF specification or IEC 61158-2. The following have been found suitable:
Non-Ex-area:
•
Siemens 6XV1 830-5BH10,
•
Belden 3076F,
•
Kerpen CEL-PE/OSCR/PVC/FRLA FB-02YS(ST)YFL.
Ex-area:
•
Siemens 6XV1 830-5AH10,
•
Belden 3076F,
•
Kerpen CEL-PE/OSCR/PVC/FRLA FB-02YS(ST)YFL
4.3
Connection data
Supply voltage
The following values are the voltages across the terminals directly at the instrument:
Current consumption
approx 15 mA for the range of voltages given above
Type
Terminal voltage
minimum
maximum
standard
9 V
32 V
EEx ia (FISCO model)
9V
17.5 V
EEx ia (Entity concept)
9 V
24 V
-
"
Made in Germany
D-79689 Maulburg
Dat./Insp.:
Order Code:
IP68 / NEMA 6P
Ser.-No.:
90 … 253 V AC 1VA
10,5 … 36 V DC 1W
10,5 … 36 V DC 0,8W
4 … 20 mA HART
2-wire
4-wire
Profibus PA
Foundation Fieldbus
HAUSER
t >85°C
TA > 70°C :
D01345-A
if modification
see sep. label
X =
Patents
PROSONIC-M
x
4
1
2
3
Before connection please note the following:
Foundation Fieldbus devices are marked on the
nameplate (1). The voltage is determined by the
Foundation Fieldbus standard and the desired safety
concept (e.g. FISCO).
Connect potential matching line to transmitter earth
terminal (4) before connecting up the device.
●
●
When you use the measuring system in hazardous areas, make sure you comply with
national standards and the specifications in the safety instructions (XA’s).
On devices supplied with a certificate, the explosion protection
is designed as follows:
Housing F12 - EEx ia:
Power supply must be intrinsically safe (e.g. FISCO).
The electronics and the current output are galvanically
separated from the antenna circuit.
●
●
Caution!
The
M is connected as follows:
Insert plug (2) into bushing (3).
Screw firmly
Ground the device according to the desired safety concept.
●
●
●
Levelflex