Compact RTD transmitter
Commissioning
Hauser
11
6
Commissioning
6.1
Installation and function check
Installation check
Monitor all connections making sure they are tight. In order to guarantee fault-free
operation, the terminal screws must be screwed tightly onto the connection cables.
Function check
Measuring the analog 4 to 20 mA output signal or following failure signals as per
NAMUR NE 43:
6.2
Switch on the device
Once the power supply has been connected, the compact RTD transmitter is
operational.
6.3
Configuration
6.3.1
Setting up using the PC configuration software
The operating and readout software is an universally applicable service and
configuration software. The operating software offers the user the following possibilities:
•
Set-up device functions
•
Measured value visualization
•
Device parameter data storage
•
Measuring point documentation
The compact RTD transmitter left the factory with a default parameter configuration. If
no customer specific configuration was mentioned on the order then the default
parameter configuration is constructed as follows:
!
Note!
If a change has been made to the measurement point then, the compact RTD
transmitter can be re-configured. In order to re-configure the parameters follow these
instructions:
•
Install the configuration software and make connection to the PC (see Chap. 5,
’Operation’).
•
For detailed operating instructions for the PC configuration software please read the
online documentation (
BA137R/09/ae
) contained in the PC operation and readout
software (see folder ’
Doc
’).
Signal (mA)
Under ranging
Standard
3.8
Over ranging
Standard
20.5
Sensor break; sensor short circuit
low
To NAMUR NE 43
≤
3.6
Sensor break; sensor short circuit
high
To NAMUR NE 43
≥
21
Sensor
Pt100 (RTD)
Connection mode
4-wire
Measuring range and
units
0 to +100 °C