NCS-TT106H-R1 HART DIN Rail

Temperature Transmitter

User Manual

Summary of Contents for NCS-TT106H-R1

Page 1: ...NCS TT106H R1 HART DIN Rail Temperature Transmitter User Manual ...

Page 2: ...fieldbus com Warning 1 It is forbidden for users to disassemble the temperature module by themselves 2 Please check if the supply voltage of temperature transmitter meets the power supply voltage requirements in themanual ...

Page 3: ...LLATION 2 2 1 DIMENSION 2 2 2 WIRING 2 3 HART TEMPERATURETRANSMIITER CONFIGURATION 4 3 1TOPOLOGY CONNECTION 4 3 2 FUNCTIONAL CONFIGURATION 5 4 MAINTENANCE 16 5 TECHNICAL SPECIFICATION 17 1 1 BASIC PARAMETER 17 1 2 RTDPARAMETER 18 1 3 THERMOCOUPLE 18 1 4 PHYSICAL PARAMETER 19 ...

Page 4: ...re transmitter and it is an indispensable field device for process control NCS TT106H R1 integrates abundant function blocks and realizes not only general measurement function but also complicated control strategy NCS TT106H R1 uses digital technology so it can connect with many types of thermocouple and thermo resistive sensors It has wide range and simple interface between field and control room...

Page 5: ...er fieldbus com 2 HART DIN Rail Temperature Transmitter NCS TT106H R1 Page Email fang siqi microcyber cn 2 INSTALLATION 2 1 Dimension Figure 2 1 Dimension of Temperature Transmitter Unit mm 2 2 Wiring Figure 2 3 Wiring ...

Page 6: ... power and bus signal share a pair of cable and it is called bus cable It is suggested the user use fieldbus special cable recommended by IEC61158 2 The signal cable and bus cable cannot share wires or wire slot with other device power wire and they shall be away from device with high power The shielded wires of bus ends shall be connected to the ground ...

Page 7: ...ode of HART smart transmitter can be divided into 4 20mA compatible mode and networking mode 4 20mA compatibility mode as shown in Figure 3 1 Power Field Communicator Features Figure 3 14 20mA compatible mode 1 Access to the upper level control system through the AI module and HART communication device 2 Mixed use of analog and digital communication methods 3 The device address is 0 HART Modem Hos...

Page 8: ...em the current on the line is fixed at 4 mA 3 Supports up to 64 device networking in short addressformat 3 2 Functional configuration The intelligent temperature transmitter supports Baldota Corporation s HartMPT configuration software HART FCG s SDC625 and other general HART configuration software for configuration debugging The following is an example of Baldota s HartMPT configuration software ...

Page 9: ...n calibrate the 4 20mA current of the online device and can also set the fixed current output 5 Variable monitoring It can periodically refresh all dynamic variables of the selected online device and display the trend curve of the current device host variable Configuration environment 1 PC with serial port operating system is Windows 2000 Windows XP 2 HART Modem and serial cable 3 Matching resista...

Page 10: ...ection range of the address is 0 to 63 2 The message can be entered up to 32 characters 3 Description can input up to 16 specified characters 4 The maximum length of the label is 8 specified characters 5 The date range is from 1900 to 2155 6 The maximum length of the assembly number is 6 specified characters Configuration information configuration The smart transmitter configuration information ca...

Page 11: ...pper limit range lower limit calibration of range and alarm current Settings etc as shown in Figure 3 4 Figure 3 4 Configuration information Damping Range 0 to 32 seconds Unit The change of PV unit directly affects the variables associated with the unit such as the upper and lower limits of the range the upper and lower limits of the sensor and so on When modifying the unit you cannot modify the u...

Page 12: ...odified you can download it to the device by pressing the Apply button Set the Range Upper Limit button with the current value set the current PV value of the device to the upper limit of the main variable range and the lower limit of therange Set the Lower Limit button with the current value Set the current PV value of the device to the lower limit of the main variable range which may change the ...

Page 13: ...Email fang siqi microcyber cn shown in Figure 3 5 Figure 3 5 Sensor configuration Sensor type supported sensor models are as below Sensor type Description 0_500R Resistance 0 500Ω 0_4000R Resistance 0 4000Ω CU50 Cu50 CU100 Cu100 PT100 PT100 PT1000 PT1000 100MV mV voltage signal range 100 100 mV ...

Page 14: ... end temperature compensation is prohibited the transmitter will not carry out the cold end temperature compensation when the cold end temperature compensation is enabled to measure internally the value of the cold end temperature compensation is measured by the internal temperature measuring chip when the cold end temperature compensation is enabled to measure externally the external two wire sys...

Page 15: ...ters is carried out in the factory only applicable to manufacturer level users RTD calibration All kinds of resistance ranges of transmitter are calibrated out of the factory only for manufacturer level users Restore factory default value Click this button all data will be restored to the default factory status Save as factory value Click this button to save the current configuration as factory va...

Page 16: ...justment value text box and click the application button 6 Select current value as blank so that the output current of the equipment is calculated according to PV value Configuration current fixed output Users can configure a fixed current output in the current calibration tab click the given fixed current value or Manual Send and fill in the fixed current value to be output click Enter Exit Fixed...

Page 17: ...ction can only be performed when device s polling address is 0 Other polling addresses are in complete digital communication mode which will prompt the error message command execution failure Variable monitoring Through the variable monitoring tab all dynamic variables of the selected equipment can be refreshed regularly and the trend curve of the main variables of the current equipment can be dis...

Page 18: ...15 http www microcyber fieldbus com HART DIN Rail Temperature Transmitter NCS TT106H R1 Page Email fang siqi microcyber cn Figure 5 2 Variable monitoring ...

Page 19: ...odule Failure Replace the temperature module with others for testing Reading Error Temperature Module Connection Failure Check sensor short circuit open circuit and earthing Check sensor Noise Disturb Adjust damping Check the house earthing Check if the terminal is moist Check the cable is away from the strong electromagnetic interference Software Configuration Check sensor type configuration Chec...

Page 20: ...ds ofThermocouple 100mV 100mV voltage signal Channel Single RTD Wiring 2 wire 3 wire 4 wire Bus Power HART 11 35 VDC Bus Signal HART current mode Electric isolation 1000VAC Working Temperature 40 85 Humidity Range 5 95 RH Start Time 5s Refresh Time 0 5s EMC GB T 18268 1 2010 Protection Terminal IP00 housing IP20 Voltage effect 0 005 V Alarm signal Alarm output can be set as 3 5 23 mA Upper lower l...

Page 21: ... 35Ω 0 015Ω PT100 200 850 0 15 0 003 PT1000 200 850 0 15 0 005 CU50 50 150 0 15 0 005 CU100 50 150 0 10 0 003 RTD Other Parameter Wiring 2 3 4 Common Mode Rejection 70dB 50Hz and 60Hz Series Mode Rejection 70dB 50Hz and 60Hz 1 3 Thermocouple Thermocouple Parameter at NormalTemperature Signal type Suggested range Accuracy 25 Temperature drift per mV 100mV 100mV 0 025mV 0 001 mV B 500 1810 0 77 0 05...

Page 22: ... 1768 0 75 0 023 S 0 1768 0 70 0 023 T 200 400 0 35 0 015 Thermocouple OtherParameter Compensation Accuracy 0 5 Sensor Type B E J N K R S T 100mV 100mV Common Mode Rejection 70dB 50Hz and 60Hz Series Mode Rejection 70dB 50Hz and 60Hz Temperature Effect 50ppm 1 4 Physical Parameter Dimension 22 5 110 99mm Housing Material Nylon ...

Page 23: ...er NCS TT106H R1 Page Email fang siqi microcyber cn YOUR FIELDBUS EXPERT CONTACT INFORMATION Address 17 8 Wensu Street Hunnan New District Shenyang China Website www microcyber fieldbus com Phone 86 24 31217278 86 24 31217280 Fax 86 24 31217338 Email fang siqi microcybe cn ...