Trouble-shooting
Compact RTD transmitter
14
Hauser
9
Trouble-shooting
9.1
Trouble-shooting instructions
If faults occur after commissioning or during measurement always start any fault finding
sequence using the following checklists. The user is guided to the possible fault cause
and its removal by question and answer.
9.2
Application errors without messages
9.2.1
General application errors
9.2.2
Application errors for RTD connection (Pt100)
Error
Cause
Action/cure
No communication
4 wire connection incorrect
Re-connect correctly (see connection
diagram)
No power supply on the 2-wire
connection
Check the current loop
Power supply too low (< 10 V)
Check power supply
Defective interface cable
Check interface cable
Defective interface
Check PC interface
Defective device
Replace device
Error
Cause
Action/cure
Fault current
(
≤
3.6 mA or
≥
21 mA)
No power supply on the M12x1
micro-connector
Check current loop; the supply
should be > 10 V
Defective device
Replace device
Error
Cause
Action/cure
Measured value incorrect/
inaccurate
Faulty sensor installation
Install sensor correctly
Heat conducted by sensor
Take note of sensor installation point
Transmitter setup faulty (number of
wires)
Change device function ’Connection
mode’
Transmitter setup faulty (scale)
Change scale
Offset incorrectly set
Check offset