Description of device parameters
Cerabar PMP23 IO-Link
48
Hauser
Current output (OU2)
Value for 4 mA (STL)
Navigation
Application → Current output (OU2) → Value for 4 mA (STL)
Description
Assignment of the pressure value which should correspond to the 4 mA value.
It is possible to invert the current output. To do so, assign the pressure upper range value
to the lower measuring current.
Note
Enter the value for 4 mA in the selected pressure unit anywhere within the measuring
range. The value can be entered in increments of 0.1 (increment depends on the
measuring range).
Options
No selection. The user is free to edit the values.
Factory setting
0.0 or as per order specifications
Value for 20 mA (STU)
Navigation
Application → Current output (OU2) → Value for 20 mA (STU)
Description
Assignment of the pressure value which should correspond to the 20 mA value.
It is possible to invert the current output. To do so, assign the pressure lower range value
to the upper measuring current.
Note
Enter the value for 20 mA in the selected pressure unit anywhere within the measuring
range. The value can be entered in increments of 0.1 (increment depends on the
measuring range).
Options
No selection. The user is free to edit the values.
Factory setting
Upper measuring limit or as per order specifications.
Pressure applied for 4mA (GTL)
Navigation
Application → Current output (OU2) → Pressure applied for 4mA (GTL)