Cerabar PMP23 IO-Link
Commissioning
Hauser
35
9.7
Application examples
9.7.1
Compressor control with hysteresis function
Example: The compressor is started when the pressure drops below a certain value. The
compressor is switched off when a certain value is exceeded.
1. Set the switch point to 2 bar (29 psi)
2. Set the switchback point to 1 bar (14.5 psi)
3. Configure the switch output as an "NC contact" (HNC function)
The compressor is controlled by the defined settings.
9.7.2
Pump control with hysteresis function
Example: The pump should switch on when 2 bar (29 psi) is reached (increasing pressure)
and switch off when 1 bar (14.5 psi) is reached (decreasing pressure).
1. Set the switch point to 2 bar (29 psi)
2. Set the switchback point to 1 bar (14.5 psi)
3. Configure the switch output as an "NO contact" (HNO function)
The pump is controlled by the defined settings.