Description of device parameters
Cerabar PMP23 IO-Link
44
Hauser
Simulation Switch Output (OU1)
Navigation
Diagnosis → Simulation Switch Output (OU1)
Description
The simulation affects the process data only. It does not affect the physical switch output.
If a simulation is active, a warning to this effect is displayed so that it is obvious to the user
that the device is in the simulation mode. A warning is communicated via IO-Link (C485 -
simulation active). The simulation must be ended actively via the menu. If the device is
disconnected from the power supply during the simulation and power is then resupplied,
the simulation mode is not resumed, and instead the device continues operation in the
measuring mode.
Options
• Off
• ou1 = high
• ou1= low
Simulation Current Output (OU2)
Navigation
Diagnosis → Simulation Current Output (OU2)
Description
Simulation affects the process data and the physical current output.
If a simulation is active, a warning to this effect is displayed so that it is obvious to the user
that the device is in the simulation mode. A warning is communicated via IO-Link (C485 -
simulation active). The simulation must be ended actively via the menu. If the device is
disconnected from the power supply during the simulation and then power is resupplied
afterwards, the simulation mode is not resumed, and instead the device continues
operation in the measuring mode.
Options
• Off
• 4 mA
• 8 mA
• 12 mA
• 16 mA
• 20 mA
• 21.95 mA
• 3.5 mA