Description of device parameters
Cerabar M, Deltapilot M
78
Hauser
13.8 Expert → Measurement → Level
Unit before lin. (025)
Description
Select the unit for the measured value display for the level .
Note
The purpose of the selected unit is to describe the measured value only, i.e., the measured
value is not converted if a new output unit is selected.
Example
• Current measured value: 0.3 ft
• New output unit: m
• New measured value: 0.3 m
Selection
• %
• mm, cm, m
• ft, inch
• m
3
, in
3
• l, hl
• ft
3
• gal, Igal
• kg, t
• lb
Factory setting
%
Calibration mode (027)
Write permission
Operator/Maintenance/Expert
Description
Select the calibration mode.
Selection
• Wet
Wet calibration is performed by filling and emptying the vessel. In the event of two dif-
ferent levels, the level, volume, mass or percentage value entered is assigned to the pres-
sure measured at this point in time ("Empty calib." and "Full calib." parameters).
• Dry
Dry calibration is a theoretical calibration. For this calibration, you specify two pressure/
level value pairs via the following parameters: "Empty calib.", "Empty pressure", "Full
calib.", "Full pressure".
Factory setting
Wet
Empty calib. (028)
Write permission
Operator/Maintenance/Expert