Installation
Hauser
27
4.5.2
FMB50
Level measurement
A0028492
• Always install the device below the lowest measuring point.
• Do not install the device at the following positions:
• in the filling curtain
• in the tank outlet
• in the suction area of a pump
• at a point in the tank which could be affected by pressure pulses from the agitator.
• The calibration and functional test can be carried out more easily if you mount the device
downstream from a shutoff device.
• The Deltapilot M must also be insulated in the case of media that can harden when cold.
Pressure measurement in gases
Mount the Deltapilot M with the shutoff device above the tapping point so that any con-
densate can flow into the process.
Pressure measurement in vapors
• Mount the Deltapilot M with the siphon above the tapping point.
• Fill the siphon with liquid before commissioning. The siphon reduces the temperature to
almost ambient temperature.
Pressure measurement in liquids
Mount the Deltapilot M with the shutoff device below or at the same level as the tapping
point.
4.5.3
Supplementary installation instructions
Sealing the probe housing
• No moisture may enter the housing when installing or operating the device, or when
establishing the electrical connection.
• Always firmly tighten the housing cover and the cable entries.
4.5.4
Seal for flange mounting
NOTICE
Corrupted measurement results.
The seal is not allowed to press against the process isolating diaphragm as this could affect
the measurement result.
‣
Ensure that the seal is not touching the process isolating diaphragm.