Pressure Testing of the Gas Supply System

1.  To check the inlet pressure to the gas valve, a 1/8” (3mm) N.P.T. 

plugged tapping, accessible for test gauge connection, must 

be placed immediately upstream of the gas supply connection 

to the appliance.

2.  The appliance and is individual shutoff valve must be discon-

nected from the gas supply piping system during any pressure 

testing of that system at test pressures in excess of 1/2 psig 

(3.5 kPa).

3. The appliance must be isolated from the gas supply piping 

system by closing its individual manual shutoff valve during 

any pressure testing of the gas supply piping system at test 

pressures equal to or less than 1/2 psig (3.5 kPa).

Attention!

 If one of the above procedures results in pressures in 

excess of 1/2 psig (14” w.c.) (3.5 kPa) on the appliance gas valve, 

it will result in a hazardous condition.

Checking Manifold Pressure

Both  Propane  and  Natural  Gas  valves  have  a  built-in  pressure 

regulator in the gas valve. Natural Gas models will have a manifold 

pressure of approximately 4.0” w.c. (.996kPa) at the valve outlet with 

the inlet pressure to the valve from a minimum of 5.0” w.c. (1.24kPa). 

Propane Gas models will have a manifold pressure approximately 

10.0” w.c. (2.49kPa) at the valve outlet with the inlet pressure to the 

valve from a minimum of 11.0” w.c. (2.739kPa) for the purpose of 

input adjustment to a maximum of 13.0” w.c. (3.237kPa).
A  1/8”  (3mm)  N.P.T.  plugged  tapping,  accessible  for  test  gauge 

connection, is located on the outlet side of the gas control.

The built-in regulator comes on at approximately 1/4th pressure 

and full on in 10 seconds.

TOP VIEW OF VALVE

PRESSURE REGULATOR

OUTLET PRESSURE TAP

GAS OUTLET

PILOT GAS OUTLET

PILOT ADJUSTMENT

SCREW BENEATH

COVER SCREW

MANUAL GAS COCK KNOB

RED RESET BUTTON

INLET PRESSURE TAP

GAS INLET

WRENCH BOSS

VENT

Figure 5

High Altitudes

For altitudes/elevations above 2,000 feet (610m), input ratings should 

be reduced at the rate of 4 percent for each 1,000 feet (305m) above 

sea level. Canadian High Altitudes for locations having an elevation 

above mean sea level between 2,000 feet (610m) and 4,500 feet 

(1370m), the manifold pressure is to be decreased from 4.0” w.c. 

(.996kPa) to 3.2” (.797kPa) w.c. for Natural Gas and from 10.0” w.c. 

(2.49kPa) to 8.0” w.c. (1.992kPa) for Propane Gas.

Piezo Pilot Ignitor Instructions

Depressing the red button completely causes a spark to occur at 

the pilot. This is a substitute for a match which requires opening 

the pilot hole cover.

To light the pilot, it is important that the electrode be 1/8” (3mm) 

from  the  thermocouple.  The  spark  must  occur  at  the  point  the 

burner flame hits the thermocouple. The end of the electrode will 

be red hot with the pilot on.
On a new installation with air in the gas line, it is suggested that a 

match be used. The match will light the pilot faster than the piezo 

under this condition.

Attention!

 The 7/8” (22mm) strain relief bushing is located within 

the same yellow envelope as the Installation Instructions and 

Owner’s Manual.

Attaching Furnace to Wall

When attaching furnace to the wall remove that portion of baseboard 

and molding on the wall which is behind the furnace. Attach furnace 

to wall, at the outer casing top, with (2) toggle bolts provided and 

to floor, at the outer casing bottom, with (2) #10 x 1 1/2” (38mm) 

screws provided.

Attention!

 The screw holes on the outer casing bottom are off-set 

above the floor approximately 3/8” (9.5mm). Do not over-tighten 

screws and distort the off-set on the outer casing bottom. Distortion 

of the outer casing bottom will not allow the lower front panel to be 

attached to the furnace.

Gas Supply

Check all local codes for requirements, especially for the size and 

type of gas supply line required. On Natural Gas lines less than 15’ 

(4.5m) long, us (1/2” (13mm) pipe; on longer runs, use 3/4” (19mm) 

iron pipe or equal. On Propane Gas lines please consult Propane 

Gas supplier.

Installing a New Main Gas Shut-Off

Each appliance should have its own manual gas shut-off.
A manual main gas shut-off should be located in the vicinity of the 

unit. Where none exists, or where its size or location is not adequate, 

contact your local authorized installer for installation or relocation.

Compounds used on threaded joints of gas piping shall be resistant 

to the action of liquefied petroleum gases. The gas lines must be 

checked for leaks by the installer. This should be done with a soap 

solution watching for bubbles on all exposed connections, and if 

unexposed, a pressure test should be made.

Never use an exposed flame to check for leaks. Appliance must 

be disconnected from piping at inlet of control valve and pipe 

capped or plugged for pressure test. Never pressure test with 

appliance connected; control valve will sustain damage!

A gas valve and ground joint union should be installed in the gas 

line upstream of the gas control to aid in servicing. It is required by 

the National Fuel Gas Code that a drip line be installed near the gas 

inlet. This should consist of a vertical length of pipe tee connected 

into the gas line that is capped on the bottom in which condensation 

and foreign particles may collect.

GAS SUPPLY PIPING

1/8(3mm)NPT PLUGGED HOLE

FOR TEST GAGE

GROUND JOINT UNION

3”(76mm)MINIMUM

MANUAL SHUT-OFF VALVE

GAS SUPPLY
INLET

1/8 (3mm) NPT PLUGGED HOLE

FOR TEST GAGE

GAS

VALVE

Figure 4

Method of Installing a Tee Fitting Sediment Trap

The use of the following gas connectors is recommended:

–ANS Z21.24 Appliance Connectors of Corrugate Metal Tubing 

and Fittings

–ANS Z21.45 Assembled Flexible Appliance Connectors of Other 

Than All-Metal Constructions

The above connectors may be used if acceptable by the authority 

having jurisdiction.

Summary of Contents for FAW55SPPXLP-1

Page 1: ...ately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING If not installed operated and maintained in accordance with the manufacturer s instructions this product could expose you to substance...

Page 2: ...nclosure 36 914mm for rooms up to 118 1 2 301cm in height DV648DBD 4 102mm Oval to Round flue adapter kit CONVERSION KITS Part Number Description Used On 682161 Propane to Natural FAW55SPPXLP 1 682270 Natural to Propane FAW55SPPXNAT 1 Important All correspondence should refer to complete Model No Serial No and type of gas NOTICE During initial firing of this unit its paint will bake out and smoke ...

Page 3: ...o indicate effects of an improperly sized venting system formation of condensate leakage spillage etc and shall specify the following test procedure WARNING CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death The following steps shall be followed...

Page 4: ...s can adsorb or absorb onto or into walls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity Propane Gas may stratify in a closed area and the odor intensity could vary at different levels Since it is heavier than air there may be more odor at lower levels Always be sensitive to the slightest gas odor If you detect any od...

Page 5: ... of 10 feet 3m 2 This furnace must not be connected to a chimney flue serving a separate solid fuel burning appliance 3 Uninsulated Single Wall Metal Pipe shall not be used outdoors in cold climates for venting gas utilization equipment 4 Attention ThisFanTypeVentedWallFurnaceisequippedwith a vent safety switch In the event of spillage of flue products due to improper venting the vent safety switc...

Page 6: ...on center studs will not allow the furnace to be recessed into the wall unless a stud is repositioned A template is proved in furnace carton for locating gas line connec tion Also refer to Figure 2 for positioning the furnace on wall and for locating gas line connection Locating Gas Supply The gas line can enter the furnace either though the floor or wall The gas line opening should be made at thi...

Page 7: ...e gas line it is suggested that a match be used The match will light the pilot faster than the piezo under this condition Attention The 7 8 22mm strain relief bushing is located within the same yellow envelope as the Installation Instructions and Owner s Manual Attaching Furnace to Wall Whenattachingfurnacetothewallremovethatportionofbaseboard and molding on the wall which is behind the furnace At...

Page 8: ...it passes through combustibles 10 3m OR LESS 3 9m MIN 2 6m MIN Figure 8 Proper Pilot Flame The correct pilot flame Figure 6 will be blue extending past the thermocouple The flame will surround the thermocouple just be low the tip Natural Gas pilots require adjusting when the inlet gas pressure is above 5 w c 1 245kPa Remove the pilot cover screw on the control valve Figure 5 and turn the adjustmen...

Page 9: ...s available in the supply tubing the pilot orifice and or pilot burner is probably restricted by a spider web Clean pilot assembly and relight If Pilot Does Not Remain On After Releasing Knob 1 Follow instructions and hold button down longer and harder 2 Determine if pilot flame extends past thermocouple if not adjust input or clean pilot burner 3 Replace thermocouple if millivolts read less than ...

Page 10: ...STOP Read safety information above 2 Turn off all electric power to the appliance 3 Remove control access panel lower front panel 4 Turn gas control knob clockwise to OFF GAS CONTROL KNOB SHOWN IN OFF POSITION 5 Wait ten 10 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information above If you don t smell gas go to the next st...

Page 11: ... first floor ceiling and one pair of fire stop spacers at each successive ceiling level C 4 102mm Oval In The Wall wall parts purchase locally 1 Type B 1 oval pipe 2 Type B 1 oval elbows 3 Single story type B 1 gas vents require a baseplate and one pair of ceiling plate spacers 4 Multi story type B 1 gas vents require a baseplate one pair of ceiling plate spacers at the first floor ceiling and one...

Page 12: ...808 PILOT TUBING W FERRULES 25 DV562 LOWER FRONT PANEL 26 DV824 FRONT BURNER 27 P8842 MAIN BURNER ORIFICE NATURAL GAS TWO REQUIRED 27 P8853 MAIN BURNER ORIFICE PROPANE GAS TWO REQUIRED 28 DV687 MANIFOLD AND PLATE ASSEMBLY 29 M148 MANIFOLD GASKET 30 DV064 COVER PLATE FOR OBSERVATION HOLE 31 DV847 BURNER DOOR NATURAL GAS 31 DV973 BURNER DOOR PROPANE GAS 32 DV775 SEAL BRACKET 33 M147 GASKET TUBING SE...

Page 13: ...37406 5 0320 Page 13 ...

Page 14: ...ase and can be ordered by your Service Person or Dealer Proof of purchase is required for warranty parts All parts listed in the Parts List have a Part Number When ordering parts first obtain the Model Number and Serial Number from the name plate on your equipment Then determine the Part Number not the Index Number and the Description of each part from the fol lowing illustration and part list Be ...

Page 15: ...ale cancelled check or payment record should be kept to verify purchase date and establish warranty period Ready access to the appliance for service What Is Not Covered Damages that might result from the use misuse or improper installation of this appliance Travel diagnostic costs and freight charges on warranted parts to and from the factory Claims that do not involve defective workmanship or mat...

Page 16: ...www empirecomfort com Empire Comfort Systems Inc Belleville IL If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question please contact your dealer ...

Page 17: ...e maison voisine Suivre les instructions du fournisseur de gaz S il est impossible de joindre le fournisseur de gaz appeler le service d incendie L installation et l entretien doivent être exécutés par un installateur qualifié une agence de service ou par le fournisseur de gaz INSTALLATEUR Laissez cette notice avec l appareil CONSOMMATEUR Conservez cette notice pour consultation ultériure AVERTISS...

Page 18: ...ie arrière extension maximale de 10 po 254 mm registre réglable DV 651DB Boîtier d évent 356 mm 14 po pour les pièces jusqu à 96 1 2 po 245 cm de hauteur DV 665DB Boîtier d évent 610 mm 24 po pour les pièces jusqu à 270 5 cm 106 1 2 de hauteur DV 666DB Boîtier de ventilation 914 mm 36 po pour les pièces d une hauteur maximale de 301 cm 118 1 2 po DV648DBD Kit adaptateur de fumée de 4 po 102 mm ova...

Page 19: ...nt indiquer les effets d un système de ventilation de taille inadéquate formation de condensat fuite déversement etc et doivent spécifier la procédure d essai suivante AVERTISSEMENT DANGER D EMPOISONNEMENT AU MONOXYDE DE CAR BONE Le fait de ne pas suivre les étapes décrites ci dessous pour chaque appareil raccordé au système d évacuation mis en service pour rait entraîner un empoisonnement au mono...

Page 20: ...de gaz peut être adsorbée ou absorbée sur ou dans les murs maçonnerie et d autres matériaux et tissus dans une chambre Ceci enlèvera une quantité de l odeur du gaz affaiblissant l intensité de la senteur Le propane peut stratifier dans un endroit fermé et l intensité de l odeur peut varier à différents niveaux Puisque le propane est plus pesant que l air l odeur peut être plus prononcée à un bas n...

Page 21: ...et de Combustion Les radiateurs muraux doivent être installés dans un endroit où la facilité delaventilationpermetunecombustiondegazsatisfaisanteetunéchappe ment convenable sous des conditions normales Dans les bâtiments de construction conventionnelle de brique ou de pierre sans fenêtre et porte étanche l infiltration est normalement adéquate pour fournir l air pour la combustion et la dilution d...

Page 22: ...sur un mur Le radiateur a une largeur de 16 406mm et étant donné que la distance normale entre les montants du mur est de 16 406mm le radiateur pourra être encastré seulement si un montant est changé de place Un guide est fourni dans l emballage du radiateur pour vous aider à local iser la connexion pour la ligne de gaz Aussi référer à la Figure 2 pour positionner le radiateur sur le mur et pour l...

Page 23: ...ues Enlever l assemblage de la fichede3 914mm ducompartimentdescontrôles aubas duradiateur 2 Enlever l entrée défonçable de 7 8 22mm du côté du panneau ap proprié 3 Introduirelebouchondenylondel assemblagedelafichede3 914mm dans l ouverture de 7 8 22mm sur le côté du panneau 4 Brancherlebouchondenylondel assemblagedelafichede3 914mm à la fiche de nylon sur le harnais de fils électriques 5 Placer l...

Page 24: ... brûleur débrancher l alimentation de gaz à la valve et enlever les huit vis qui tiennent la porte du brûleur Après avoir enlevé la porte du brûleur de la chambre de combustion enlever le brûleur arrière le brûleur de la veilleuse et le brûleur de devant Avec les brûleurs de devant et arrière enlevés faire entrer de l eau avec force dans la bande d ouvertures et sécher avec une pression d air ET F...

Page 25: ... l évent avec une remise à zéro manuelle est situé sur le coupe tirage 3 Replacer le panneau de devant en haut Si l interrupteur de sûreté de l évent avec remise à zéro manuelle continu d arrêter le débit de gaz aux brûleurs principaux un technicien d entretien qualifié doit être contacté pour vérifier s il y a une évacuation inadéquate une obstruction dans le tuyau d échappement ou si l interrupt...

Page 26: ...ompris près du plancher pour déceler une odeur de gaz Si vous sentez le gaz ARRÊTER Suivre B dans les informations de sécurité ci dessus Si vous ne sentez aucun gaz aller à la prochaine étape 6 Enlever le couvercle d accès à la veilleuse situé sur la chambre de combustion 7 Trouverlaveilleuse suivreletuyau demétalàpartirducontrôledegaz La veilleuse est située entre les deux tuyaux des brûleurs der...

Page 27: ...umette 2 Utiliser le piezo allumeur à 30 secondes d intervalles jusqu à ce qu elle s allume Si l Électrode ne Produit Pas d Étincelle 1 Vérifier les connexions des fils électriques 2 Vérifier la distance du brûleur de la veilleuse au bout de l électrode Doit être entre 1 8 3mm et 3 16 5mm Le fil de l électrode et le bout doivent être éloignés à plus de 1 4 6mm de toutes autres pièces métalliques E...

Page 28: ...6 Bâti du ventilateur 10 11759 Panneau du côté 11 DV627 Panneau de devant en haut 12 R1619 Manchon 13 DV823 Assemblage du coupetirage 14 R1749 Interrupteur de sûreté de l évent 15 R1587 Assemblage des fils pour la sûreté de l évent 16 R1536 Manchon 17 11765 Assemblage du compartiment d interrupteur 18 DV832 Couvercle du compartiment d interrupteur 19 R630 Contrôle de tolérance 20 R1941 Contrôle du...

Page 29: ...37406 5 0320 Page 13 Empire Comfort Systems Inc Nine Eighteen Freeburg Ave Belleville Illinois 62222 0529 ...

Page 30: ...a plaque du plafond 4 Les évents à gaz de type B 1 pour plus d un étage exige une plaque de base une paire d entretoises pour la plaque du pla fond au plafond du premier étage et une paire d entretoises pour l arrêt de feu à chaque niveau de plafond successif L espace entre les montants autour des évents à gaz doit être sans obstruc tion et sans papier de construction ACCESSOIRES Numéro pièce Desc...

Page 31: ... paiement pour attester de la date d achat et établir la période de garantie Accès immédiat à l appareil pour la réparation Ce qui n est pas couvert Dommages pouvant résulter de l emploi de l emploi abusif ou d une installation incorrecte de cet appareil Frais de déplacement de diagnostic et de transport des pièces sous garantie vers et depuis l usine Réclamations qui n impliquent pas des défauts ...

Page 32: ... Empire Comfort Systems Inc Belleville Illinois Pour toute question générale concernant nos produits veuillez nous envoyer un courriel à info empirecomfort com Pour toute question d entretien ou de réparation veuillez contacter votre revendeur ...

Reviews: